2005-06-03 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- PROVIDE STRUCTURAL BUCK DETAILS FOR
 SWING DOOR AT GARAGE. SEE PRODUCT
 APPROVAL FOR SIZE REQUIRED.
 **NOTE: IT'S THE DESIGNER OF RECORD THE
 ONE WHO PROVIDES THIS INFORMATION NOT
 THE PRODUCT APPROVAL. SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001 AND SECTION
 1707.4.4.2 FBC 2001.
  
 2- SECTION 1/A6 IS INCOMPLETE. IS
 MISSING 2ND FLOOR FRAMING ON THE OTHER
 SIDE OF THE WALL. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 3- A) PROVIDE UPLIFT CALCULATIONS FOR
 ROOF TRUSSES TO CLARIFYWHY UPLIFT
 CALCULATIONS SHOWN ON PLANS ARE THE SAME
 FOR THE FIRST STORY ROOF AS THE ONES FOR
 THE SECOND STORY ROOF. SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 B) CLARIFY WHY USING CONNECTORS ON
 SECOND FLOOR ROOF THAT DON'T PROVIDE
 RESISTANCE FOR LATERAL LOADS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 C) CLARIFY WHY USING STRONGER CONNECTORS
 FOR ROOF AT FIRST FLOOR THAN AT SECOND
 FLOOR ROOF. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 4- SHEET A6: UNABLE TO FIND SIMPSON
 LUSC212 AND LUS212 CONNECTORS IN THE
 SIMPSON CATALOGUE. WHERE WERE THEY TAKEN
 FROM? PROVIDE COMPLETE CONNECTOR
 INFORMATION AND PRODUCT APPROVAL. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 5- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR: A) USP CONNECTORS
 SPECIFIED ON PLANS.
  
 B) GARAGE DOORS. DRAWINGS SUBMITTED ARE
 NOT LEGIBLE.
  
 6-A) ON FIRST SUBMITTAL PACKAGE THERE
 WAS A PRODUCT APPROVAL FOR RAILING
 SYSTEM TO BE USED IN THE HOUSE. IT WAS
 NOT GOOD BECAUSE IT WAS TO BE ANCHORED
 TO CONCRETE SLAB. NOW, THERE IS NO
 SUBMITTAL FOR RAILINGS NOW.
 PROVIDE COMPLETE SPECS AND DETAILS FOR
 CONSTRUCTION OF RAILING SYSTEMS. SPECIFY
 ALL CONNECTORS, ETC. DESIGN TO COMPLY
 WITH SEC. 1608.2 FBC 2001.
  
 B) TYPICAL STAIR DETAIL ON SHEET A10
 DOESN'T MATCH STAIRS SHOWN ON PLANS.
 LOOK AT FIRST AND LAST STEP. ALSO, NEED
 TO SPECIFY ALL FRAMING CONNECTORS FOR
 POSTS ETC.
 AND, REVISE CONNECTOR TO BE ATTACHED TO
 MASONRY. NEED TO SPECIFY MASONRY
 CONNECTOR. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 7- SECTIONS SHOWN ON SHEET A11 DON'T
 APPLY TO THIS PROJECT. PROVIDE SECTIONS
 THAT APPLY. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  