2005-06-03 00:00:00 | BUILDING REVIEW CHECKLIST: |
| |
| 1- PROVIDE STRUCTURAL BUCK DETAILS FOR |
| SWING DOOR AT GARAGE. SEE PRODUCT |
| APPROVAL FOR SIZE REQUIRED. |
| **NOTE: IT'S THE DESIGNER OF RECORD THE |
| ONE WHO PROVIDES THIS INFORMATION NOT |
| THE PRODUCT APPROVAL. SECTION 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001 AND SECTION |
| 1707.4.4.2 FBC 2001. |
| |
| 2- SECTION 1/A6 IS INCOMPLETE. IS |
| MISSING 2ND FLOOR FRAMING ON THE OTHER |
| SIDE OF THE WALL. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| |
| 3- A) PROVIDE UPLIFT CALCULATIONS FOR |
| ROOF TRUSSES TO CLARIFYWHY UPLIFT |
| CALCULATIONS SHOWN ON PLANS ARE THE SAME |
| FOR THE FIRST STORY ROOF AS THE ONES FOR |
| THE SECOND STORY ROOF. SECTION 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| |
| B) CLARIFY WHY USING CONNECTORS ON |
| SECOND FLOOR ROOF THAT DON'T PROVIDE |
| RESISTANCE FOR LATERAL LOADS. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| C) CLARIFY WHY USING STRONGER CONNECTORS |
| FOR ROOF AT FIRST FLOOR THAN AT SECOND |
| FLOOR ROOF. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| |
| 4- SHEET A6: UNABLE TO FIND SIMPSON |
| LUSC212 AND LUS212 CONNECTORS IN THE |
| SIMPSON CATALOGUE. WHERE WERE THEY TAKEN |
| FROM? PROVIDE COMPLETE CONNECTOR |
| INFORMATION AND PRODUCT APPROVAL. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| 5- PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL FOR: A) USP CONNECTORS |
| SPECIFIED ON PLANS. |
| |
| B) GARAGE DOORS. DRAWINGS SUBMITTED ARE |
| NOT LEGIBLE. |
| |
| 6-A) ON FIRST SUBMITTAL PACKAGE THERE |
| WAS A PRODUCT APPROVAL FOR RAILING |
| SYSTEM TO BE USED IN THE HOUSE. IT WAS |
| NOT GOOD BECAUSE IT WAS TO BE ANCHORED |
| TO CONCRETE SLAB. NOW, THERE IS NO |
| SUBMITTAL FOR RAILINGS NOW. |
| PROVIDE COMPLETE SPECS AND DETAILS FOR |
| CONSTRUCTION OF RAILING SYSTEMS. SPECIFY |
| ALL CONNECTORS, ETC. DESIGN TO COMPLY |
| WITH SEC. 1608.2 FBC 2001. |
| |
| B) TYPICAL STAIR DETAIL ON SHEET A10 |
| DOESN'T MATCH STAIRS SHOWN ON PLANS. |
| LOOK AT FIRST AND LAST STEP. ALSO, NEED |
| TO SPECIFY ALL FRAMING CONNECTORS FOR |
| POSTS ETC. |
| AND, REVISE CONNECTOR TO BE ATTACHED TO |
| MASONRY. NEED TO SPECIFY MASONRY |
| CONNECTOR. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| |
| 7- SECTIONS SHOWN ON SHEET A11 DON'T |
| APPLY TO THIS PROJECT. PROVIDE SECTIONS |
| THAT APPLY. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| |