Plan Review Notes For Permit 05011505 |
Permit Number |
05011505 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-02-14 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1) SHT SP1 SANITARY RISER DIAGRAM DOES | | NOT REFLECT THE FLOOR PLAN, NOR DOES IT | | MEET CODE REQUIREMENTS. | | A) FIRST FLOOR BATHROOMS SHOW TUBS ON | | THE FLOOR PLAN, BUT SHOW SHOWERS ON THE | | SANT. RISER DIAGRAM. SECTION 104.2.1. | | B) ALL SHOWERS, TUBS, BIDET, & WASH | | MACHINE REQUIRE A TRAP. SECTION 901.2.1. | | C) STANDPIPE FOR THE WASH MACHINE SHALL | | BE UPSTREAM OF THE TRAP. PLEASE SHOW ON | | THE RISER DIAGRAM. SECTION 104.2.1. | | | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | |
|