2005-02-08 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PANEL "B" IS SHOWN AS MLO IN THE
 NOTES, HAS NO OCP IN METER MAIN, AND NO
 APPEARANT DISCONNECTING MEANS PER
 225.32.
  
 2} THERE ARE 75 RECESSED LIGHTS IN THE
 LOAD CALCS, BUT ONLY 24 ON PLANS. PLEASE
 CORRELATE.
  
 3} ELECTRIC WATER HEATER IS SHOWN ON THE
 PLAN, DOES NOT APPEAR ON THE PANEL
 SCHEDULE. ALSO CALCULATE PER 442.13.
  
 4} A SMOKE DETECTOR IS REQUIRED PER
 8-1.4.1.6.2 NFPA-72, OUTSIDE SLEEPING
 AREA, "IMMEDIATE VICINITY".
  
 5} ISLAND RECEPTACLES REQUIRED TO BE GFI
 PER 210.8(A)(6).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  