Plan Review Notes For Permit 05011505 |
Permit Number |
05011505 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-02-08 00:00:00 | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PANEL "B" IS SHOWN AS MLO IN THE | | NOTES, HAS NO OCP IN METER MAIN, AND NO | | APPEARANT DISCONNECTING MEANS PER | | 225.32. | | | | 2} THERE ARE 75 RECESSED LIGHTS IN THE | | LOAD CALCS, BUT ONLY 24 ON PLANS. PLEASE | | CORRELATE. | | | | 3} ELECTRIC WATER HEATER IS SHOWN ON THE | | PLAN, DOES NOT APPEAR ON THE PANEL | | SCHEDULE. ALSO CALCULATE PER 442.13. | | | | 4} A SMOKE DETECTOR IS REQUIRED PER | | 8-1.4.1.6.2 NFPA-72, OUTSIDE SLEEPING | | AREA, "IMMEDIATE VICINITY". | | | | 5} ISLAND RECEPTACLES REQUIRED TO BE GFI | | PER 210.8(A)(6). | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|