2005-02-18 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- WHEN APPLYING FOR BUILDING PERMIT, |
| PLEASE PAY IMPACT FEES AND BRING BACK |
| STAMPED DRAWINGS AND PAID RECEIPT. |
| ALSO, PROVIDE COPY OF RECORDED NOTICE OF |
| COMMENCEMENT. |
| |
| 2- CLARIFY IF USING IMPACT GLAZING OR |
| STORM SHUTTERS. BOTH PACKAGES WERE |
| SUBMITTED. IF USING STORM SHUTTERS, |
| THEN, PROVIDE COMPLETE INFORMATION. |
| |
| 3- REVISE HANDRAIL HEIGHT SHOWN ON STAIR |
| DETAIL. SHEET A10. HANDRAIL NEED TO BE |
| BETWEEN 34" AND 38" (NOT 42"). SECTION |
| 1007.5.1 FBC 2001 EXCEPTION #3. |
| **NOTE: GUARDRAIL AND HANDRAIL ARE NOT |
| THE SAME. |
| |
| 4-SPECIFY ROOF TILE FASTENING AS REQ'D |
| BY SEC. 104.2.1.1 CITY AMENDMENTS TO FBC |
| |
| 5- GARAGE DOOR SIZE SPECIFIED ON DOOR |
| SCHEDULE IS NOT THE SAME AS SHOWN ON |
| ELEVATIONS. REVISE AS REQUIRED. |
| |
| 6- PROVIDE SURVEY WITH LAYOUT THAT |
| MATCHES PLANS SUBMITTED. |
| |
| 7- OWNER/AGENT NEEDS TO SIGN AND DATE |
| THE ENERGY CALCULATIONS FORM. |
| |
| 8- PROVIDE SOIL TEST REPORT. |
| |
| 9- PROVIDE STRUCTURAL BUCK DETAILS FOR |
| SWING AND SLIDING GLASS DOORS. (SEE |
| PRODUCT APPROVAL FOR SIZE OF BUCK REQ'D) |
| SECTION 104.2.1.2 SECTION 104.2.1.2 OF |
| CITY AMENDMENTS TO FBC 2001 AND SECTION |
| 1707.4.4.2 FBC 2001. |
| |
| 10- SPECIFY DRAFSTOPPING MATERIALS AND |
| LOCATION ON 2ND FLOOR FRAMING PLAN AS |
| REQUIRED BY SEC. 2305.2.2(1) FBC 2001. |
| |
| 11- PLEASE, PROVIDE ONLY THE DETAILS |
| THAT APPLY TO THIS PROJECT TO EXPEDITE |
| AND CLARIFY REVIEW PROCESS. |
| |
| 12- PROVIDE COMPLETE WALL SECTION/DETAIL |
| AT EAST WALL SHOWING HOW ARE ROOF |
| TRUSSES STRUCTURALLY SUPPORTED ON |
| LEDGER. SPECIFY ALL FASTENERS. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| 13- PROVIDE UPLIFT CALCULATIONS FOR ROOF |
| TRUSSES(INCLUDING LATERAL FORCES) AND |
| EXPLAIN WHY USING CONNECTORS ON 2ND |
| FLOOR ROOF TRUSSESTHAT DON'T |
| PROVIDE RESISTANCE TO LATERAL FORCES. |
| (*NOTE: IT'S THE DESIGNER OF RECORD |
| RESPONSIBILITY TO CALCULATE THE LOADS |
| NOT THE TRUSS ENGINEER*. REVISE NOTES ON |
| SHEETS A6 AND A7). |
| |
| 14- PROVIDE SMOKE DETECTOR IN FIRST FL. |
| CLOSE TO THE STAIRS AS REQ'D BY SECTION |
| 905.2.2 FBC 2001. |
| |
| 15- PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL FOR: A) DOUBLE ENTRY DOORS AS |
| SHOWN ON PLANS. |
| B) 8'-0" HIGH SWING DOORS AS SHOWN ON |
| PLANS (NOT 7'-0"HIGH AS SUBMITTED) |
| C) RAILING SYSTEM TO BE INSTALLED IN |
| FRAMED FLOORS, NOT CONCRETE SLAB. |
| PROVIDE COMPLETE DETAILS FOR WOOD FRAMED |
| |
| FLOORS AS SHOWN ON PLANS. |
| D) GARAGE DOOR INCLUDING DRAWINGS OF |
| MODEL TO BE INSTALLED. |
| E) FIXED WINDOWS. |
| |
| 16- SHEET A1: A) REVISE DETAIL F1. NEED |
| FOOTING TO BE 12 MIN. BELOW GRADE (NOT |
| 8"). SEC. 1804.1.3 FBC 2001. |
| B) SPECIFY REQUIRED DEPTH BELOW GRADE |
| ON DETAIL F3. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| |
| 17- SHEET A6: BUCKETS SPECIFIED FOR |
| BALCONY CONSTRUCTION ARE WOOD TO WOOD |
| JOIST HANGERS. NEED BUCKET WITH |
| SPECIFICATIONS TO BE INSTALLED ON |
| CONCRETE BLOCK WALL. (ALSO, WHERE ARE |
| LUSC 212-3 CONNECTORS ON SIMPSON |
| CATALOGUE?) |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| |
| 18- SHEET A7: SPECIFY CONNECTORS FOR |
| HAND FRAMED HIPS AND VALLEY RAFTERS. |
| SECTION 104.2.1.2 CITY AMENDMENTS TO FBC |
| |
| 19- DETAILS/SECTIONS ON SHEET A11 DON'T |
| APPLY TO THIS PROJECT. |
| |