2005-02-18 00:00:00BUILDING REVIEW CHECKLIST:
 1- WHEN APPLYING FOR BUILDING PERMIT,
 PLEASE PAY IMPACT FEES AND BRING BACK
 STAMPED DRAWINGS AND PAID RECEIPT.
 ALSO, PROVIDE COPY OF RECORDED NOTICE OF
 COMMENCEMENT.
  
 2- CLARIFY IF USING IMPACT GLAZING OR
 STORM SHUTTERS. BOTH PACKAGES WERE
 SUBMITTED. IF USING STORM SHUTTERS,
 THEN, PROVIDE COMPLETE INFORMATION.
  
 3- REVISE HANDRAIL HEIGHT SHOWN ON STAIR
 DETAIL. SHEET A10. HANDRAIL NEED TO BE
 BETWEEN 34" AND 38" (NOT 42"). SECTION
 1007.5.1 FBC 2001 EXCEPTION #3.
 **NOTE: GUARDRAIL AND HANDRAIL ARE NOT
 THE SAME.
  
 4-SPECIFY ROOF TILE FASTENING AS REQ'D
 BY SEC. 104.2.1.1 CITY AMENDMENTS TO FBC
  
 5- GARAGE DOOR SIZE SPECIFIED ON DOOR
 SCHEDULE IS NOT THE SAME AS SHOWN ON
 ELEVATIONS. REVISE AS REQUIRED.
  
 6- PROVIDE SURVEY WITH LAYOUT THAT
 MATCHES PLANS SUBMITTED.
  
 7- OWNER/AGENT NEEDS TO SIGN AND DATE
 THE ENERGY CALCULATIONS FORM.
  
 8- PROVIDE SOIL TEST REPORT.
  
 9- PROVIDE STRUCTURAL BUCK DETAILS FOR
 SWING AND SLIDING GLASS DOORS. (SEE
 PRODUCT APPROVAL FOR SIZE OF BUCK REQ'D)
 SECTION 104.2.1.2 SECTION 104.2.1.2 OF
 CITY AMENDMENTS TO FBC 2001 AND SECTION
 1707.4.4.2 FBC 2001.
  
 10- SPECIFY DRAFSTOPPING MATERIALS AND
 LOCATION ON 2ND FLOOR FRAMING PLAN AS
 REQUIRED BY SEC. 2305.2.2(1) FBC 2001.
  
 11- PLEASE, PROVIDE ONLY THE DETAILS
 THAT APPLY TO THIS PROJECT TO EXPEDITE
 AND CLARIFY REVIEW PROCESS.
  
 12- PROVIDE COMPLETE WALL SECTION/DETAIL
 AT EAST WALL SHOWING HOW ARE ROOF
 TRUSSES STRUCTURALLY SUPPORTED ON
 LEDGER. SPECIFY ALL FASTENERS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 13- PROVIDE UPLIFT CALCULATIONS FOR ROOF
 TRUSSES(INCLUDING LATERAL FORCES) AND
 EXPLAIN WHY USING CONNECTORS ON 2ND
 FLOOR ROOF TRUSSESTHAT DON'T
 PROVIDE RESISTANCE TO LATERAL FORCES.
 (*NOTE: IT'S THE DESIGNER OF RECORD
 RESPONSIBILITY TO CALCULATE THE LOADS
 NOT THE TRUSS ENGINEER*. REVISE NOTES ON
 SHEETS A6 AND A7).
  
 14- PROVIDE SMOKE DETECTOR IN FIRST FL.
 CLOSE TO THE STAIRS AS REQ'D BY SECTION
 905.2.2 FBC 2001.
  
 15- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR: A) DOUBLE ENTRY DOORS AS
 SHOWN ON PLANS.
 B) 8'-0" HIGH SWING DOORS AS SHOWN ON
 PLANS (NOT 7'-0"HIGH AS SUBMITTED)
 C) RAILING SYSTEM TO BE INSTALLED IN
 FRAMED FLOORS, NOT CONCRETE SLAB.
 PROVIDE COMPLETE DETAILS FOR WOOD FRAMED
  
 FLOORS AS SHOWN ON PLANS.
 D) GARAGE DOOR INCLUDING DRAWINGS OF
 MODEL TO BE INSTALLED.
 E) FIXED WINDOWS.
  
 16- SHEET A1: A) REVISE DETAIL F1. NEED
 FOOTING TO BE 12 MIN. BELOW GRADE (NOT
 8"). SEC. 1804.1.3 FBC 2001.
 B) SPECIFY REQUIRED DEPTH BELOW GRADE
 ON DETAIL F3. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 17- SHEET A6: BUCKETS SPECIFIED FOR
 BALCONY CONSTRUCTION ARE WOOD TO WOOD
 JOIST HANGERS. NEED BUCKET WITH
 SPECIFICATIONS TO BE INSTALLED ON
 CONCRETE BLOCK WALL. (ALSO, WHERE ARE
 LUSC 212-3 CONNECTORS ON SIMPSON
 CATALOGUE?)
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 18- SHEET A7: SPECIFY CONNECTORS FOR
 HAND FRAMED HIPS AND VALLEY RAFTERS.
 SECTION 104.2.1.2 CITY AMENDMENTS TO FBC
  
 19- DETAILS/SECTIONS ON SHEET A11 DON'T
 APPLY TO THIS PROJECT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.