Plan Review Notes
Plan Review Notes For Permit 05011394
Permit Number 05011394
Review Stop B
Sequence Number 1
Notes
Date Text
2005-02-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05011394
 ADD: 340 ELLAMAR RD
 CONT: J & G CARPENTRY
 TEL: (561)333-7704
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 1)ALL INFORMATION, DRAWINGS, SPECIF-
 ICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 CITY AMENDMENTS 104.2.1
  
 2) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 DISCREPANCY, THE PERMIT APPLICATION
 INDICATES (5) WINDOWS BEING CHANGED OUT,
 WHERE AS THE PLANS INDICATE (7)?
  
 3) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG.
 THE NOA SUBMITTED DOESN'T HAVE THE
 STATEWIDE APPROVAL, REQUIRING LOCAL
 APPROVAL, A COPY OF THE LOCAL APPROVAL
 FORM IS SUBMITTED, THE MANUFACTURE IS TO
 FILL OUT THIS FORM.
  
 4) PROVIDE INFORMATION REQUIED BY CHAP
 3401.7.2.4. INDICATE THE TOTAL SQ FT
 AREA OF EXTERIOR GLAZING( WINDOWS &
 SLIDING GLASS DOORS), IF THE AREA OF
 GLAZING BEING REPLACED IS GREATER THAN
 25% OF THE TOTAL GLAZING THEN THIS AREA
 BEING REPLACED, THEN THESE OPENINGS
 SHALL REQUIRE EITHER IMPACT GLAZING OR
 STORM SHUTTERS WITH IMPACT
 TESTING.PROVIDE CALCULATIONS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026