2005-01-31 00:00:00DENIED:
  
 1) FIRE ALARM SYSTEMS THAT SUPERVISE
 FIRE SPRINKLER SYSTEMS SHALL BE UL
 CERTIFICATED AND HAVE DOCUMENTS
 ATTESTING TO THIS CERTIFICATION PRIOR TO
 FINAL APPROVAL OF THE FIRE ALARM
 SYSTEM.
  
 2) THE FIRE ALARM SYSTEM SHALL BE CLASS
 "A" OR FULLY ADDRESSSABLE.
  
 3) THE WEST PALM BEACH FIRE MARSHAL
 OFFICE REQUIRES DUCT SMOKE DETECTORS TO
 SEND A GENERAL FIRE ALARM NOT A
 SUPERVISORY.
  
  