Plan Review Notes For Permit 05011327 |
Permit Number |
05011327 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-02-09 00:00:00 | DENIED: | | 1.PLAN SHEET A-1 INDICATES THE WALL | | SEAPARATING CLASSROOM 208 AND THE | | CORRIDOR IS 1 HOUR RATED.PLAN SHEET M1 | | THE NEW 24" X 14" RETURN AIR DUCT DOES | | NOT INDICATE A FIRE DAMPER AS REQUIRED | | BY THE 2001 FBC(M)607.1.2 & 607.6. | | | | PLANS ARE OTHERWISE CODE COMPLIANT. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. | | |
|