Notes |
Date |
Text |
2005-01-31 00:00:00 | DENIED: | | TRANSFER GRILLES ARE NOT SIZED FROM THE | | MASTER SUITE & BEDROOM #3.THE R/A | | GRILLE FROM BEDROOM/DEN #2 IS INDICATED | | AS 8" X 8", WHICH IS NOT SIZED IN | | ACCORDANCE WITH 2001 FBC(M)601.4 | | EXCEPTION #2.TRANSFER GRILLES ARE TO | | BE A MINIMUM OF 50 SQ INCHES PER 100 CFM | | OF SUPPLY AIR INTO THAT SPACE.PLEASE | | NOTE ALL AIR INTO THE MASTER SUITE IS TO | | BE INCLUDED FOR PROPER SIZING OF THE | | TRANSFER AIR GRILLE (INCLUDE ALL SUPPLY | | AIR INTO THE MASTER BEDROOM, BATHROOM | | AND CLOSET AREAS). | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|