Plan Review Notes
Plan Review Notes For Permit 05011284
Permit Number 05011284
Review Stop M
Sequence Number 1
Notes
Date Text
2005-01-31 00:00:00DENIED:
 TRANSFER GRILLES ARE NOT SIZED FROM THE
 MASTER SUITE & BEDROOM #3.THE R/A
 GRILLE FROM BEDROOM/DEN #2 IS INDICATED
 AS 8" X 8", WHICH IS NOT SIZED IN
 ACCORDANCE WITH 2001 FBC(M)601.4
 EXCEPTION #2.TRANSFER GRILLES ARE TO
 BE A MINIMUM OF 50 SQ INCHES PER 100 CFM
 OF SUPPLY AIR INTO THAT SPACE.PLEASE
 NOTE ALL AIR INTO THE MASTER SUITE IS TO
 BE INCLUDED FOR PROPER SIZING OF THE
 TRANSFER AIR GRILLE (INCLUDE ALL SUPPLY
 AIR INTO THE MASTER BEDROOM, BATHROOM
 AND CLOSET AREAS).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.