2005-02-01 00:00:00*****UNSAT *****
  
 1)NOTE: PLEASE SHOW CIRCUITING FOR
 LIGHTING IN FRONT TENANT SPACE.
  
 2)NOTE: PLEASE VERIFIFY SHOW WINDOW
 RECEPTS REQUIRED PER 210.62.
 RECEPTS ARE SHOWN ABOVE WINDOWS WHICH
 MENTIONS FOR SIGN? PLEASE SEE 600.5, NO
 OTHER MAY BE ON SIGN CIRCUIT.
  
 3)NOTE: PLEASE SHOW LOCATION OF NEW
 PANEL "B", THIS COULD NOT BE LOCATED ON
  
 PLANS.
  
 4)NOTE: PLEASE SEE CONDUIT SIZES ON
 PANEL SCHEDULE FOR FEEDERS AND CORRELATE
 WITH RISER DIAGRAM.
 215.5
  
 5)NOTE: PLEASE SEE LOAD CALCULATIONS ARE
 NOT SHOWN FOR NEW PANEL "B", ONLY SHOWS
 CONNECTED LOAD.
 PLEASE VERIFY CONTINUOUS LOADS AT 125%.
 215.03,230.42 ETC.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE BE AWARE OF ANY POSSIBLE COMMENTS
 FROM OTHER REVIEWERS WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
  