Plan Review Notes
Plan Review Notes For Permit 05011200
Permit Number 05011200
Review Stop P
Sequence Number 1
Notes
Date Text
2005-02-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT D1 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS.
 A) WASH MACHINE REQUIRES A TRAP AND A
 STANDPIPE. SECTIONS 1002.1 & 802.4
 B) WASH MACHINE AND LAUNDRY SINK SHALL
 NOT BE CONNECTED TO THE STACK ON A
 DOUBLE SANITARY TEE PATTERN. SEPARATE
 TEES REQUIRED. SECTION 706.3
 C) LANUDRY SINK IS MISLABELED AS A LAV
 SECTION 104.2.1.
 D) CLEANOUT ON LAUNDRY SINK/WASH
 MACHINE SHALL BE 4' ABOVE THE FLOOR FOR
 ACCESS. SECTION 708.10.
 E) BATHROOM BEHIND THE BAR SINK SHOWS A
 SHOWER ON THE RISER DIAGRAM, BUT SHOWS A
 TUB ON THE FLOOR PLAN. PLEASE CLARIFY.
 SECTION 104.2.1.
  
  