Date |
Text |
2005-02-04 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1) SHT D1 SANITARY RISER DIAGRAM DOES | | NOT REFLECT THE FLOOR PLAN, NOR DOES IT | | MEET CODE REQUIREMENTS. | | A) WASH MACHINE REQUIRES A TRAP AND A | | STANDPIPE. SECTIONS 1002.1 & 802.4 | | B) WASH MACHINE AND LAUNDRY SINK SHALL | | NOT BE CONNECTED TO THE STACK ON A | | DOUBLE SANITARY TEE PATTERN. SEPARATE | | TEES REQUIRED. SECTION 706.3 | | C) LANUDRY SINK IS MISLABELED AS A LAV | | SECTION 104.2.1. | | D) CLEANOUT ON LAUNDRY SINK/WASH | | MACHINE SHALL BE 4' ABOVE THE FLOOR FOR | | ACCESS. SECTION 708.10. | | E) BATHROOM BEHIND THE BAR SINK SHOWS A | | SHOWER ON THE RISER DIAGRAM, BUT SHOWS A | | TUB ON THE FLOOR PLAN. PLEASE CLARIFY. | | SECTION 104.2.1. | | | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|