2005-02-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05011200
 ADD: 7160 WINDING BAY LANE
 CONT: RIF GROUP
 TEL: (561)239-5790
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET T1, DESIGN PARAMETERS, MISSING
 THE
  
 WIND IMPORTANCE FACTOR (1) AND BUILDING
 CATEGORY SEE ASCE7-98, ALSO EXPLAIN THE
 "BUILDING DESIGN AS CLOSED, KD=0.85,
 EXPLAIN ?
  
 3A) SHEET A3.0 TRUSS ANCHORS, ANCHOR(J)
 HIGH VALUE, ANCHOR (L) HIGH VALUE, SEE
 2005 USP VALUES.1609.4.3 LOAD
 REDUCTION.WHEN STRUCTURAL EFFECTS DUE
 TO
 TWO OR MORE LOADS IN COMBINATION WITH
 DEAD LOAD ARE INVESTIGATED IN LOAD
 COMBINATIONS OF 1609.4.1 OR 1609.4.2,
 THE COMBINED EFFECTS DUE TO THE TWO OR
 LOADS MULTI- PLIED BY 0.75 PLUS EFFECTS
 DUE TO DEAD LOADS SHALL NOT BE LESS
 THAN
 THE EFFECTS FROM THE LOAD COMBINATION
 OF
 THE DEAD LOAD PLUS THE LOAD PRODUCING
 THE LARGEST EFFECTS. INCREAS IN
 ALLOWABLE STRESS SPE CIFIED IN THE
 MATERIALS SECTIONS OF THIS CODE OR A
 REFRENCED STANDARD SHALL NOT BE USED
 WITH THESE LOAD COMBINATIONS EXCEPT
 THAT
 A DURATION OF LOAD INCREASE SHALL BE
 PERMITTED IN ACCORDANCE WITH CHAPTER
 23.
 3B) TRUSS ANCHORS REQUIRE LISTINGS FROM
 THE FLORIDA PRODUCT APPRVAL OR A LOCAL
 LISTING SEE ATTACHED FORM.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 4) SOILS REPORTS,PLANS,
 SPECIFICATIONS,REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 5) FIRM: JEFFERY SSILBERSTEIN ARCHITECT
 & ASSOCIATES, INC. FIRMS CERTIFICATE OF
 AUTHORIZATION NOT SHOWN FL S S
 481.219.(2)(3).
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026