2005-03-11 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 REVISION:
 ORIGINAL PERMIT IS FOR ASPHALT SHINGLES.
 PROPOSED REVISION IS TO INCLUDE MODIFIED
 BITUMEN OVER AN AREA OF FLAT ROOF.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC* 104.2.1.2THE AREAS OF FLAT AND
 PITCHED ROOF MUST BE STATED.THE
 ORIGINAL PERMIT APPLICATION FORM STATED
 1900 SQFT OF PITCHED ROOF.
  
 2) THE SUBMITTED PRODUCT APPROVAL SHEETS
 (NOA# 01-0529.01) SHALL BE MARKED, AS
 APPROPRIATE, TO IDENTIFY WHICH FLAT ROOF
 SYSTEM IS TO BE USED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS