2005-02-19 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1) ENGINEERS SHALL LEGIBLY INDICATE |
| THEIR NAME, ADDRESS, AND LICENSE NUMBER |
| ON EACH SHEET, AND IF PRACTICING THROUGH |
| A DULY AUTHORIZED ENGINEERING BUSINESS, |
| ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| NAME AND LICENSE NUMBER, AS WELL AS, THE |
| NAME, ADDRESS, AND CERTIFICATE OF |
| AUTHROIZATION NUMBER OF THE ENGINEERING |
| BUSINESS ON EACH SHEET. FAC |
| 61G15-23.002(2) & FS 471.025. - |
| SIGNATURE REQUIRED - NO INITIALS PER |
| FDPE,S RULING. |
| 2) PERSONAL SIGNATURE OF THE ARCHITECT |
| REQUIRED. G1G1-16.003 FS 481.2055 - THE |
| FOLLOWING INFORMATION MISSING FROM |
| REQUIRED TITLE BLOCK: 61G1-16.004 |
| (2) FIRM LICENSE NUMBER |
| (6) PRINTED NAME OF THE PERSON SEALING |
| THE DOCUMENT. FS 481.219 (CERTIFICATE OF |
| AUTHORIZATION). |
| 3) SHT D1.0 IN THE REMOVAL OF ANY PART |
| OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE |
| PROHIBITED. SECTION 704.5. ALL DEMO'D |
| PIPING SHALL NOT BE COVERED PRIOR TO |
| INSPECTION. |
| 4) THE FOLLOWING INFORMATION IS REQUIRED |
| ON THE PLANS TO SHOW COMPLIANCE WITH |
| SECTIONS 11-4.16, 11-4.19, & 11-4.22: |
| A) CLEAR FLOOR SPACE W/C 11-4.16.2 |
| (TURNING AREA IS NOT CLEAR FLOOR SPACE) |
| B) FLUSH CONTROLS W/C (WIDE SIDE) |
| 11-4.16.5. |
| C) HEIGHT OF LAV (34") 11-4.19.2 |
| 5) SUBMIT A DETAIL FOR THE DRINKING |
| FOUNTAIN SHOWING COMPLIANCE WITH THE |
| FOLLOWING: |
| A) SPOUT HEIGHT 11-4.15.2 |
| B) CLEARANCES/CLEAR FLOOR SPACE |
| 11-4.15.5 |
| 6) SHT M2.0 WATER RISER DIAGRAM, WATER |
| HAMMER ARRESTOR SHALL BE LOCATED NEAR |
| THE FIXTURES IN AN "EFFECTIVE RANGE" NOT |
| IN THE CEILING AS SHOWN. PDI-WH 201 AND |
| MANUF. INSTALLATION INSTRUCTIONS. |
| 7) SHT M2.0 WATER HEATER DETAIL. |
| EMERGENCY HEATER PAN DRAIN AND P&T VALVE |
| DISCHARGE LINE SHALL DRAIN TO A HUB |
| DRAIN OR A FLOOR SINK. FLOOR DRAINS ARE |
| NOT AN APPROVED INDIRECT WASTE RECEPTOR. |
| SECTIONS 802.3 & 802.3.2. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |