Plan Review Notes
Plan Review Notes For Permit 05010869
Permit Number 05010869
Review Stop P
Sequence Number 1
Notes
Date Text
2005-02-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT A-1 SHOW TURNING AREA IN EACH
 TOILET ROOMS DETAIL #2. SECTION
 11-4.22.3.
 2) SHT A-1 SHOW CLEAR FLOOR SPACE FOR
 THE LOUNGE SINK. SECTION 11-4.24.5.
 (FORWARD APPROACH REQUIRED, MAXIMUM 19"
 UNDERNEATH THE SINK).
 3) SHT A-3 DETAIL #7 FLUSH CONTROLS TO
 BE MOUNTED ON THE WIDE SIDE OF THE
 TOILET AREA. SECTION 11-4.16.5. - DETAIL
 #10 MAXIMUM SINK DEPTH TO BE 6-1/2".
 SECTION 11-4.24.4. (MAX. 7" SHOWN).
 4) SUBMIT A DETAIL FOR THE DRINKING
 SHOWING COMPLIANCE WITH 11-4.15 AND ALL
 SUBSECTIONS.
 5) SHT P0.1 PLUMBING FIXTURE SCHEDULE.
 SUBMIT MANUF. SPECIFICATION SHEETS FOR
 THE POWERSTREAM RP-1 TANKLESS WATER
 HEATER. SHEETS SHALL SHOW LISTING, AND
 INSTALLATION INSTRUCTIONS. SECTION
 303.4
 6) SHT P5.1 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS SHALL BE LOCATED IN AN
 "EFFECTIVE RANGE" NEXT TO THE FIXTURES,
 NOT IN THE CEILING AS SHOWN. PDI-WH 201
 AND MANUF INSTALL. INSTRUCTIONS.
  
  
 REVIEW BY KEN STEVENS