Plan Review Notes For Permit 05010869 |
Permit Number |
05010869 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-02-03 00:00:00 | DENIED: | | 1.PLAN SHEET M2.1, ERU-1 INDICATED IN | | THE RESTROOM AREAS.IS THIS AN EXHAUST | | UNIT?PLANS APPEAR TO HAVE THE DUCTWORK | | FROM ERU-1 TAPPING INTO THE RETURN | | DUCTWORK FROM AHU-4 & 8.PER 2001 | | FBC(M) TABLE 403.3, EXHAUST FROM | | BATHROOM AREAS SHALL NOT BE | | RECIRCULATED.EXHAUST DUCT SHALL | | TERMINATE TO THE OUTDOORS PER | | 2001FBC(M)501.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|