Plan Review Notes
Plan Review Notes For Permit 05010869
Permit Number 05010869
Review Stop M
Sequence Number 1
Notes
Date Text
2005-02-03 00:00:00DENIED:
 1.PLAN SHEET M2.1, ERU-1 INDICATED IN
 THE RESTROOM AREAS.IS THIS AN EXHAUST
 UNIT?PLANS APPEAR TO HAVE THE DUCTWORK
 FROM ERU-1 TAPPING INTO THE RETURN
 DUCTWORK FROM AHU-4 & 8.PER 2001
 FBC(M) TABLE 403.3, EXHAUST FROM
 BATHROOM AREAS SHALL NOT BE
 RECIRCULATED.EXHAUST DUCT SHALL
 TERMINATE TO THE OUTDOORS PER
 2001FBC(M)501.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.