Plan Review Notes
Plan Review Notes For Permit 05010848
Permit Number 05010848
Review Stop E
Sequence Number 1
Notes
Date Text
2005-01-24 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE INCLUDE ALL LICENSE #'S
 IN TITLE BLOCK AS REQUIRED UNDER FAC
 61G15-23.002 AND PER FS 471.023
 THIS IS REQUIRED FOR ALL TRADE SHEETS
 WHEATHER OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: PLEASE SEE SEC'S ARE SHOWN AS
 1/0'S, HOWEVER SERVICE IS SHOWN AS 200A
 METER/MAIN. . PLEASE SEE 310.16 FOR MIN
 SIZE OF SEC'S.
  
 3)NOTE: PLEASE SHOW LOAD CALCULATION AND
 SHOW CONTINUOUS LOADS AT 125%.
 220.3, 220.10.220.13 215.3,230.42 ETC.
 215.5
  
 4)NOTE: PLEASE SEE MISSING CWP AS PART
 OF THE GROUNDING ELECTRODE SYSTEM PER
 250.50
  
 5)NOTE: PLEASE SEE HAND DRAWN CHAGES ON
 PLANS ARE NOT PERMITTED TO SIGNED AND
 SEALED PLANS.
 FS 471.025 ETC.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]