Plan Review Notes For Permit 05010770 |
Permit Number |
05010770 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-01-26 00:00:00 | ****CORRECTIONS**** | | | | SAMAMTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)PROVIDE A SOILS INVESTIGATION | | REPORT, FBC1804.2.2.SOILS ENGINEER IS | | TO BE MADE AWARE OF THE SCOPE OF WORK. | | HAVE GEOTECHNICAL REPORT REVIEWED BY | | ENGINEER OF RECORD PRIOR TO | | RESUBMITTAL. | | | | 2.)REGARDING THE NOTE "REPAIRING | | CONTRACTOR TO SEARCH OUT ADDITIONAL | | CRACKS TO REPAIR", PROVIDE A | | SPECIFICATION FOR REPAIR. | | | | 3.)THE SURVEY SHOWS A DIFFERENT | | ADDRESS THAN THE LEGAL ADDRESS. | | CLARIFY. | | | | 4.)STATE OR LOCAL PRODUCT APPROVAL | | REQUIRED FOR STRUCTURAL COMPONENTS, | | FAC9B-72. | | |
|