Plan Review Notes For Permit 05010767 |
Permit Number |
05010767 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-01-28 00:00:00 | | | PLEASE CORRECT THE PLANS TO INCLUDE THE | | FOLLOWING. | | | | 1} THE ROOM WORK IS BEING DONE TO NOW IS | | A BEDROOM BY DEFINITION OF THE FLORIDA | | BUILDING CODE. THEREFORE SMOKE DETECTORS | | ARE REQUIRED PER 8-1.4.1.6.2 NFPA-72, | | INSIDE AND OUTSIDE. | | | | 2} ALL OUTLETS MUST COMPLY WITH 210.12. | | | | 3} THE ARCHITECT IS REQUIRED TO HAVE THE | | FIRM LICENSE NUMBER IN THE TITLE BLOCK | | PER 61G1-16.004 FAC. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|