Plan Review Notes For Permit 05010754 |
Permit Number |
05010754 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-01-28 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE PROVIDE A CALCULATION INCLUDI- | | NG ALL ADDED LOADS IMPOSED,ALL EXISTING | | LOADS. THE A/C,WATER HEATER AND POOL | | EQUIPMENT IN POOL HOUSE ARE NOT SHOWN ON | | THE CALC'S. | | | | 2} THERE IS NO LAUNDRY CIRCUIT IN THE | | CALCULATION PER 220.16(B). | | | | 3} THERE IS NO DRYER IN THE CALCULATION | | PER 220.18. | | | | 4} THE TWO RISER DIAGRAMS DO NOT | | CORRELATE. IS THE 150 AMP PANEL FED FROM | | THE METER OR THE200 AMP HOUSE PANEL? | | | | 5} SHOW LOCATION OF ALL SERVICE | | EQUIPMENT ON THE POOL HOUSE ON THE | | PLAN. | | | | 6} SHOW 150 AMP PANEL SCHEDULE AND | | GROUNDING PER 250.32 | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|