Plan Review Notes For Permit 05010754
Permit Number 05010754
Review Stop E
Sequence Number 1
Notes
Date Text
2005-01-28 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE A CALCULATION INCLUDI-
 NG ALL ADDED LOADS IMPOSED,ALL EXISTING
 LOADS. THE A/C,WATER HEATER AND POOL
 EQUIPMENT IN POOL HOUSE ARE NOT SHOWN ON
 THE CALC'S.
  
 2} THERE IS NO LAUNDRY CIRCUIT IN THE
 CALCULATION PER 220.16(B).
  
 3} THERE IS NO DRYER IN THE CALCULATION
 PER 220.18.
  
 4} THE TWO RISER DIAGRAMS DO NOT
 CORRELATE. IS THE 150 AMP PANEL FED FROM
 THE METER OR THE200 AMP HOUSE PANEL?
  
 5} SHOW LOCATION OF ALL SERVICE
 EQUIPMENT ON THE POOL HOUSE ON THE
 PLAN.
  
 6} SHOW 150 AMP PANEL SCHEDULE AND
 GROUNDING PER 250.32
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026