Plan Review Notes
Plan Review Notes For Permit 05010748
Permit Number 05010748
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-01-27 00:00:00DENIED:
 1) PLEASE PROVIDE SHOP DRAWING OF THE
 FLOOR PLAN ON THE LOCATION OF THE
 DEVICES.
  
 2) NEW FIRE ALARM SYSTEMS SHALL BE UL
 LISTED FOR CENTRAL STATION SERVICE.
  
 3) ALL NEW FIRE ALARM SYSTEMS THAT
 SUPERVISE FIRE SPRINKLER SYSTEMS SHALL
 BE UL CERTIFICATED AND HAVE DOCUMENTS
 ATTESTING TO THIS CERTIFICATION PRIOR TO
 FINAL APPROVAL OF THE FIRE ALARM
 SYSTEM.
  
 4) THE FIRE ALARM SYSTEM SHALL BE CLASS
 "A" OR FULLY ADDRESSABLE.
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722