Plan Review Notes
Plan Review Notes For Permit 05010713
Permit Number 05010713
Review Stop E
Sequence Number 1
Notes
Date Text
2005-01-24 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE FLOOR PLANS INDICATING
 LOCATION OF THE EMERGENCY AND EXIT
 LIGHTS. ALSO SHOW LIGHTING AND CIRCUITS
 SO COMPLIANCE WITH 700.18 CAN BE
 DETERMINED.
  
 2} THE LOAD CALCULATION SHOULD BE
 DETERMINED PER 220.3 NOT 220.30.
  
 3} THE 100 AMP. ELEVATER EQUIPMENT
 PANEL
 SHOWN AS MUST BE FED WITH #3 CU PER
 310.16.*
  
 4} THE 100 AMP PANELS ON THE 1ST FLOOR
 MUST BE FED WITH #3 CU PER 310.16.*
  
 * IF FEEDERS ARE PROTECTED BY
 APPROPRIATE OCP PROVIDE PANEL SCHEDULE
 INDICATING SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026