Plan Review Notes For Permit 05010713 |
Permit Number |
05010713 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-01-24 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PROVIDE FLOOR PLANS INDICATING | | LOCATION OF THE EMERGENCY AND EXIT | | LIGHTS. ALSO SHOW LIGHTING AND CIRCUITS | | SO COMPLIANCE WITH 700.18 CAN BE | | DETERMINED. | | | | 2} THE LOAD CALCULATION SHOULD BE | | DETERMINED PER 220.3 NOT 220.30. | | | | 3} THE 100 AMP. ELEVATER EQUIPMENT | | PANEL | | SHOWN AS MUST BE FED WITH #3 CU PER | | 310.16.* | | | | 4} THE 100 AMP PANELS ON THE 1ST FLOOR | | MUST BE FED WITH #3 CU PER 310.16.* | | | | * IF FEEDERS ARE PROTECTED BY | | APPROPRIATE OCP PROVIDE PANEL SCHEDULE | | INDICATING SAME. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|