2005-01-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT A4 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS.
 A) EVERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN SHALL CONNECT ABOVE THE
 CENTERLINE OF THE HORIZONTAL DRAIN PIPE.
 SECTION 905.3. (SEE BIDET IN M/B AND
 SHOWER IN BATH #3).
 B) WASH MACHINE SHALL HAVE A STANDPIPE
 PER SECTIONS 1002.1 & 802.4
 C) CLEANOUT FOR WASH MACHINE SHALL BE
 4' ABOVE THE FLOOR. SECTION 708.10
  
  