2005-03-25 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)SEE PREVIOUS LIST, INDICATE METHOD |
| OF INSTALLATION AND WHICH PRODUCT IS |
| BEING INSTALLED.A RESPONSE WAS |
| PROVIDED - "WITH A DRILL".THIS DOES |
| NOT SHOW CODE COMPLIANCE.THERE ARE TWO |
| ACCORDIAN SHUTTERS WITH VARIOUS METHODS |
| OF ATTACHMENT ON YOUR PRODUCT APPROVAL. |
| PLEASE CIRCLE WHICH PRODUCT YOU ARE |
| USING AND CIRCLE THE DRAWING WHICH SHOWS |
| METHOD OF INSTALLATION (INSIDE MOUNT, |
| WALL MOUNT, ETC).SHEET 6 HAS THE |
| TAPCON FASTENERS FOR THE 6.8 ACCORDIAN |
| SHUTTER HIGHLIGHTED, BUT BOTH THE 2" |
| EDGE DISTANCE AND 3" EDGE DISTANCE ARE |
| HIGHLIGHTED.IS THIS CORRECT? |
| |
| 2.)IN RESPONSE TO THE PREVIOUS REQUEST |
| TO FILL OUT THE SCHEDULE FOR |
| INSTALLATION, A WALL PRESSURE WAS |
| PROVIDED OF -30/-175.OPENINGS HAVE A |
| POSITIVE AND NEGATIVE PRESSURE; HOW HAVE |
| YOU ARRIVED AT TWO NEGATIVE NUMBERS? |
| PLEASE PROVIDE CORRECT DP.IF THIS IS A |
| ONE STORY SINGLE FAMILY DWELLING, THE |
| -30 IS TOO LOW AND THE -175 IS TOO HIGH. |
| SEE FBC TABLE1606.2B AND D, AND FIGURE |
| 1606.2(C). |
| |
| 3.)SEE PREVIOUS LIST, ITEM #3, FLORIDA |
| STATE PRODUCT APPROVAL OR LOCAL PRODUCT |
| APPROVAL REQUIRED IN ADDITION TO TEST |
| REPORT, WWW.FLORIDABUILDING.ORG. |
| |
| 4.)SHOW EMERGENCY MEANS OF ESCAPE |
| FBC1005.4.4. |