Plan Review Notes
Plan Review Notes For Permit 05010528
Permit Number 05010528
Review Stop B
Sequence Number 2
Notes
Date Text
2005-03-25 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST, INDICATE METHOD
 OF INSTALLATION AND WHICH PRODUCT IS
 BEING INSTALLED.A RESPONSE WAS
 PROVIDED - "WITH A DRILL".THIS DOES
 NOT SHOW CODE COMPLIANCE.THERE ARE TWO
 ACCORDIAN SHUTTERS WITH VARIOUS METHODS
 OF ATTACHMENT ON YOUR PRODUCT APPROVAL.
 PLEASE CIRCLE WHICH PRODUCT YOU ARE
 USING AND CIRCLE THE DRAWING WHICH SHOWS
 METHOD OF INSTALLATION (INSIDE MOUNT,
 WALL MOUNT, ETC).SHEET 6 HAS THE
 TAPCON FASTENERS FOR THE 6.8 ACCORDIAN
 SHUTTER HIGHLIGHTED, BUT BOTH THE 2"
 EDGE DISTANCE AND 3" EDGE DISTANCE ARE
 HIGHLIGHTED.IS THIS CORRECT?
  
 2.)IN RESPONSE TO THE PREVIOUS REQUEST
 TO FILL OUT THE SCHEDULE FOR
 INSTALLATION, A WALL PRESSURE WAS
 PROVIDED OF -30/-175.OPENINGS HAVE A
 POSITIVE AND NEGATIVE PRESSURE; HOW HAVE
 YOU ARRIVED AT TWO NEGATIVE NUMBERS?
 PLEASE PROVIDE CORRECT DP.IF THIS IS A
 ONE STORY SINGLE FAMILY DWELLING, THE
 -30 IS TOO LOW AND THE -175 IS TOO HIGH.
 SEE FBC TABLE1606.2B AND D, AND FIGURE
 1606.2(C).
  
 3.)SEE PREVIOUS LIST, ITEM #3, FLORIDA
 STATE PRODUCT APPROVAL OR LOCAL PRODUCT
 APPROVAL REQUIRED IN ADDITION TO TEST
 REPORT, WWW.FLORIDABUILDING.ORG.
  
 4.)SHOW EMERGENCY MEANS OF ESCAPE
 FBC1005.4.4.