Plan Review Notes For Permit 05010511 |
Permit Number |
05010511 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-01-25 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)DOCUMENTS PREPARED BY AN ARCHITECT | | AND SUBMITTED FOR PUBLIC RECORD ARE TO | | BE SIGNED, SEALED AND DATED (SHEETS | | A3.07, LS102) FAC61G15-23.002. | | | | 2.)SHEET A3.07 HAS REVISIONS NOT | | APPROVED BY THE CITY.PLEASE NOTE THAT | | REVISION #50, DATED 7/21/04 SHOWS THE | | USE OF FOAM.THIS WAS DENIED ON | | 4/12/04; ARCHITECTURAL TRIM ON | | BUILDINGS | | LOCATED IN THE FIRE DISTRICT SHALL BE | | CONSTRUCTED OF APPROVED NONCOMBUSTIBLE | | MATERIALS OR FIRE RETARDANT TREATED | | WOOD, F102.2.7 CITY OF WEST PALM BEACH | | AMENDMENTS TO THE FBC, FBC1404.PLEASE | | CLARIFY. | | | | 3.)PRIOR TO RESUBMITTAL, HAVE THE | | AWNING PLANS REVIEWED BY DOR. | | | | 4.)THE ENGINEERING IS GENERIC. | | INDICATE WHICH ANCHORS, SIZES, ETC. ARE | | TO BE USED. |
|