2005-01-22 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 FOLLOWING INFORMATION REQUIRED FOR GAS
 PERMIT:
  
 1. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 2. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 3. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 4. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 5) MANUF SHEET INDICATED 579 GGFE AND A
 HAND WRITTEN BTU 52.399. PLEASE CLARIFY.
 SECTION 104.2.1
 6) PERMIT WILL NOT BE ISSUED UNTIL AN
 ELECTRIC PERMIT FOR THE GENERATOR IS
 APPLIED FOR. ALSO IF THE GENERATOR IS
 LOCATED OUTSIDE THE BUILDING, APPROVAL
 BY ZONING IS REQUIRED.
  