2005-01-22 00:00:00 | DENIED | | REFERENCE: FBC-2001 FUEL GAS | | FBC-2001 CHAPTER 1 | | | | FOLLOWING INFORMATION REQUIRED FOR GAS | | PERMIT: | | | | 1. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE BEING USED. | | 2. SUBMIT CALCULATIONS FOR COMBUSTION | | AIR (IF APPLICABLE) PER FBC-2001 FUEL | | GAS CODE SECTION 304. | | 3. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | 4. SUBMIT A DETAIL SHOWING THE TYPE, | | LOCATION, SIZE AND TERMINATION OF THE | | GAS VENTS PER FBC-2001 FUEL GAS CODE | | SECS. 502 THRU 506. | | 5) MANUF SHEET INDICATED 579 GGFE AND A | | HAND WRITTEN BTU 52.399. PLEASE CLARIFY. | | SECTION 104.2.1 | | 6) PERMIT WILL NOT BE ISSUED UNTIL AN | | ELECTRIC PERMIT FOR THE GENERATOR IS | | APPLIED FOR. ALSO IF THE GENERATOR IS | | LOCATED OUTSIDE THE BUILDING, APPROVAL | | BY ZONING IS REQUIRED. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|