2005-01-11 00:00:00 | PROVISO: | | REMOVAL OF AHU AND DUCTWORK CAN BE DONE | | PLEASE PROVIDE THE FOLLOWING PRIOR TO | | WORK COMMENCING: | | 1.LAYOUT OF DUCTWORK; PROVIDE DUCT | | SIZE, MATERIAL AND GRILLE/CAN SIZE. | | 2.AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED. | | 3.DUCT SMOKE DETECTOR SHALL HAVE | | NOTIFICATION TO ALARM/STROBE IN | | NORMMALLY OCCUPIED AREAS, PER 2001 | | FBC(M)606.4.1 #2. | | 4.INDICATE TERMINATION OF THE EXHAUST | | TO THE "RE-LOCATED" HOOD.COMPLY WITH | | 2001 FBC(M)506.3.14.3. | | 5.PROVIDE OUTSIDE AIR CALCULATIONS PER | | 2001 FBC(M) TABLE 403.3. | | 6.INDICATE OUTSIDE AIR INTAKE, DUCT | | SIZE AND MATERIAL. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|