Plan Review Notes
Plan Review Notes For Permit 05010477
Permit Number 05010477
Review Stop M
Sequence Number 1
Notes
Date Text
2005-01-11 00:00:00PROVISO:
 REMOVAL OF AHU AND DUCTWORK CAN BE DONE
 PLEASE PROVIDE THE FOLLOWING PRIOR TO
 WORK COMMENCING:
 1.LAYOUT OF DUCTWORK; PROVIDE DUCT
 SIZE, MATERIAL AND GRILLE/CAN SIZE.
 2.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED.
 3.DUCT SMOKE DETECTOR SHALL HAVE
 NOTIFICATION TO ALARM/STROBE IN
 NORMMALLY OCCUPIED AREAS, PER 2001
 FBC(M)606.4.1 #2.
 4.INDICATE TERMINATION OF THE EXHAUST
 TO THE "RE-LOCATED" HOOD.COMPLY WITH
 2001 FBC(M)506.3.14.3.
 5.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) TABLE 403.3.
 6.INDICATE OUTSIDE AIR INTAKE, DUCT
 SIZE AND MATERIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.