Date Text
2006-02-18 00:00:00PLUMBING PLAN REVIEW EXAMINER
 PAUL SCHMITZ 561-805-6692
 [email protected]
 FBC PLUMBING 2004
 FBC BUILDING 2004, CH 11
 DENIED THIRD TIME
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1) SHTS 1 AND 2 PREVIOUS NOTES NOT
 ADDRESSED.
  
 2) SHT 6 SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET
 CODE REQUIREMENTS.
  
 3) 11-4.15 DRINKING FOUNTAINS AND WATER
 COOLERS
 ?11-4.15.2 SPOUT HEIGHT. SPOUTS SHALL
 BE NO HIGHER THAN 36 INCHES (915
 MM), MEASURED FROM THE FLOOR OR GROUND
 SURFACES TO THE SPOUT OUTLET (SEE
 FIGURE 11-27(A)).
 ?11-4.15.4 CONTROLS. CONTROLS SHALL
 COMPLY WITH ?11-4.27.4.UNIT
 CONTROLS SHALL BE FRONT MOUNTED OR
 SIDE MOUNTED NEAR THE FRONT EDGE.
 ?11-4.15.5 CLEARANCES.
 ?11-4.15.5(1) WALL- AND POST-MOUNTED
 CANTILEVERED UNITS SHALL HAVE A
 CLEAR KNEE SPACE BETWEEN THE BOTTOM
 OF THE APRON AND THE FLOOR OR
 GROUND AT LEAST 27 INCHES (685 MM)
 HIGH, 30 INCHES (760 MM) WIDE, AND
 17 INCHES TO 19 INCHES (430 MM TO
 485 MM) DEEP (SEE FIGURE 11-27(A)
 AND FIGURE 11-27(B)).SUCH UNITS
 SHALL ALSO HAVE A MINIMUM CLEAR
 FLOOR SPACE 30 INCHES BY 48 INCHES
 (760 MM BY 1220 MM) TO ALLOW A
 PERSON IN A WHEELCHAIR TO APPROACH
 THE UNIT FACING FORWARD.
  
 4)?11-4.22 TOILET ROOMS.
 ?11-4.22.1 MINIMUM NUMBER. TOILET
 FACILITIES REQUIRED TO BE ACCESSIBLE
 BY ?11-4.1 SHALL COMPLY WITH ?11-4.22.
 ACCESSIBLE TOILET ROOMS SHALL BE
 ON AN ACCESSIBLE ROUTE.
 ?11-4.22.2 DOORS.
 ?11-4.22.2(1) ALL DOORS TO
 ACCESSIBLE TOILET ROOMS SHALL COMPLY
 WITH
 ?11-4.13.DOORS SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE REQUIRED
 FOR ANY FIXTURE.
  
 EXCEPTION: ALL NEW SINGLE-FAMILY
 HOUSES, DUPLEXES, TRIPLEXES,
 CONDOMINIUMS, AND TOWNHOUSES SHALL
 PROVIDE AT LEAST ONE BATHROOM,
 LOCATED WITH MAXIMUM POSSIBLE
 PRIVACY, WHERE BATHROOMS ARE PROVIDED ON
 HABITABLE GRADE LEVELS, WITH A DOOR THAT
 HAS A 29 INCH CLEAR OPENING.
 HOWEVER, IF ONLY A TOILET ROOM IS
 PROVIDED AT GRADE LEVEL, SUCH TOILET
 ROOM SHALL HAVE A CLEAR OPENING OF
 NOT LESS THAN 29 INCHES.
  
 ?11-4.22.3 CLEAR FLOOR SPACE. THE
 ACCESSIBLE FIXTURES AND CONTROLS
 REQUIRED IN ?11-4.22.4, ?11-4.22.5,
 ?11-4.22.6, AND ?11-4.22.7 SHALL BE
 ON AN ACCESSIBLE ROUTE.AN
 UNOBSTRUCTED TURNING SPACE COMPLYING
 WITH 11-
 4.2.3 SHALL BE PROVIDED WITHIN AN
 ACCESSIBLE TOILET ROOM.THE CLEAR FLOOR
 SPACE AT FIXTURES AND CONTROLS, THE
 ACCESSIBLE ROUTE, AND THE TURNING
 SPACE MAY OVERLAP.
  
 ?11-4.22.4 WATER CLOSETS. IF TOILET
 STALLS ARE PROVIDED, THEN AT LEAST
 ONE SHALL BE A STANDARD TOILET STALL
 COMPLYING WITH ?11-4.17; WHERE 6 OR
 MORE STALLS ARE PROVIDED, IN ADDITION
 TO THE STALL COMPLYING WITH
 ?11-4.17.3, AT LEAST ONE STALL 36 IN
 (915 MM) WIDE WITH AN OUTWARD
 SWINGING, SELF-CLOSING DOOR AND
 PARALLEL GRAB BARS COMPLYING WITH
 FIGURE 11-30(D) AND ?11-4.26 SHALL BE
 PROVIDED.WATER CLOSETS IN
 SUCH STALLS SHALL COMPLY WITH
 ?11-4.16.IF WATER CLOSETS ARE NOT IN
 STALLS, THEN AT LEAST ONE SHALL COMPLY
 WITH ?11-4.16.
 ?11-4.22.6 LAVATORIES AND MIRRORS. IF
 LAVATORIES AND MIRRORS ARE
 PROVIDED, THEN AT LEAST ONE OF EACH
 SHALL COMPLY WITH ?11-4.19.
 ?11-4.22.7 CONTROLS AND DISPENSERS. IF
 CONTROLS, DISPENSERS,
 RECEPTACLES, OR OTHER EQUIPMENT ARE
 PROVIDED, THEN AT LEAST ONE OF EACH
 SHALL BE ON AN ACCESSIBLE ROUTE AND
 SHALL COMPLY WITH ?11-4.27.
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  