2006-02-18 00:00:00 | PLUMBING PLAN REVIEW EXAMINER |
| PAUL SCHMITZ 561-805-6692 |
| [email protected] |
| FBC PLUMBING 2004 |
| FBC BUILDING 2004, CH 11 |
| DENIED THIRD TIME |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| |
| 1) SHTS 1 AND 2 PREVIOUS NOTES NOT |
| ADDRESSED. |
| |
| 2) SHT 6 SANITARY RISER DIAGRAM DOES NOT |
| REFLECT THE FLOOR PLAN, NOR DOES IT MEET |
| CODE REQUIREMENTS. |
| |
| 3) 11-4.15 DRINKING FOUNTAINS AND WATER |
| COOLERS |
| ?11-4.15.2 SPOUT HEIGHT. SPOUTS SHALL |
| BE NO HIGHER THAN 36 INCHES (915 |
| MM), MEASURED FROM THE FLOOR OR GROUND |
| SURFACES TO THE SPOUT OUTLET (SEE |
| FIGURE 11-27(A)). |
| ?11-4.15.4 CONTROLS. CONTROLS SHALL |
| COMPLY WITH ?11-4.27.4.UNIT |
| CONTROLS SHALL BE FRONT MOUNTED OR |
| SIDE MOUNTED NEAR THE FRONT EDGE. |
| ?11-4.15.5 CLEARANCES. |
| ?11-4.15.5(1) WALL- AND POST-MOUNTED |
| CANTILEVERED UNITS SHALL HAVE A |
| CLEAR KNEE SPACE BETWEEN THE BOTTOM |
| OF THE APRON AND THE FLOOR OR |
| GROUND AT LEAST 27 INCHES (685 MM) |
| HIGH, 30 INCHES (760 MM) WIDE, AND |
| 17 INCHES TO 19 INCHES (430 MM TO |
| 485 MM) DEEP (SEE FIGURE 11-27(A) |
| AND FIGURE 11-27(B)).SUCH UNITS |
| SHALL ALSO HAVE A MINIMUM CLEAR |
| FLOOR SPACE 30 INCHES BY 48 INCHES |
| (760 MM BY 1220 MM) TO ALLOW A |
| PERSON IN A WHEELCHAIR TO APPROACH |
| THE UNIT FACING FORWARD. |
| |
| 4)?11-4.22 TOILET ROOMS. |
| ?11-4.22.1 MINIMUM NUMBER. TOILET |
| FACILITIES REQUIRED TO BE ACCESSIBLE |
| BY ?11-4.1 SHALL COMPLY WITH ?11-4.22. |
| ACCESSIBLE TOILET ROOMS SHALL BE |
| ON AN ACCESSIBLE ROUTE. |
| ?11-4.22.2 DOORS. |
| ?11-4.22.2(1) ALL DOORS TO |
| ACCESSIBLE TOILET ROOMS SHALL COMPLY |
| WITH |
| ?11-4.13.DOORS SHALL NOT SWING |
| INTO THE CLEAR FLOOR SPACE REQUIRED |
| FOR ANY FIXTURE. |
| |
| EXCEPTION: ALL NEW SINGLE-FAMILY |
| HOUSES, DUPLEXES, TRIPLEXES, |
| CONDOMINIUMS, AND TOWNHOUSES SHALL |
| PROVIDE AT LEAST ONE BATHROOM, |
| LOCATED WITH MAXIMUM POSSIBLE |
| PRIVACY, WHERE BATHROOMS ARE PROVIDED ON |
| HABITABLE GRADE LEVELS, WITH A DOOR THAT |
| HAS A 29 INCH CLEAR OPENING. |
| HOWEVER, IF ONLY A TOILET ROOM IS |
| PROVIDED AT GRADE LEVEL, SUCH TOILET |
| ROOM SHALL HAVE A CLEAR OPENING OF |
| NOT LESS THAN 29 INCHES. |
| |
| ?11-4.22.3 CLEAR FLOOR SPACE. THE |
| ACCESSIBLE FIXTURES AND CONTROLS |
| REQUIRED IN ?11-4.22.4, ?11-4.22.5, |
| ?11-4.22.6, AND ?11-4.22.7 SHALL BE |
| ON AN ACCESSIBLE ROUTE.AN |
| UNOBSTRUCTED TURNING SPACE COMPLYING |
| WITH 11- |
| 4.2.3 SHALL BE PROVIDED WITHIN AN |
| ACCESSIBLE TOILET ROOM.THE CLEAR FLOOR |
| SPACE AT FIXTURES AND CONTROLS, THE |
| ACCESSIBLE ROUTE, AND THE TURNING |
| SPACE MAY OVERLAP. |
| |
| ?11-4.22.4 WATER CLOSETS. IF TOILET |
| STALLS ARE PROVIDED, THEN AT LEAST |
| ONE SHALL BE A STANDARD TOILET STALL |
| COMPLYING WITH ?11-4.17; WHERE 6 OR |
| MORE STALLS ARE PROVIDED, IN ADDITION |
| TO THE STALL COMPLYING WITH |
| ?11-4.17.3, AT LEAST ONE STALL 36 IN |
| (915 MM) WIDE WITH AN OUTWARD |
| SWINGING, SELF-CLOSING DOOR AND |
| PARALLEL GRAB BARS COMPLYING WITH |
| FIGURE 11-30(D) AND ?11-4.26 SHALL BE |
| PROVIDED.WATER CLOSETS IN |
| SUCH STALLS SHALL COMPLY WITH |
| ?11-4.16.IF WATER CLOSETS ARE NOT IN |
| STALLS, THEN AT LEAST ONE SHALL COMPLY |
| WITH ?11-4.16. |
| ?11-4.22.6 LAVATORIES AND MIRRORS. IF |
| LAVATORIES AND MIRRORS ARE |
| PROVIDED, THEN AT LEAST ONE OF EACH |
| SHALL COMPLY WITH ?11-4.19. |
| ?11-4.22.7 CONTROLS AND DISPENSERS. IF |
| CONTROLS, DISPENSERS, |
| RECEPTACLES, OR OTHER EQUIPMENT ARE |
| PROVIDED, THEN AT LEAST ONE OF EACH |
| SHALL BE ON AN ACCESSIBLE ROUTE AND |
| SHALL COMPLY WITH ?11-4.27. |
| |
| END OF COMMENTS, QUESTIONS 561-805-6692 |
| |
| |