Plan Review Notes
Plan Review Notes For Permit 05010378
Permit Number 05010378
Review Stop E
Sequence Number 3
Notes
Date Text
2006-01-31 00:00:00************ UNSAT 3RD REVIEW *********
  
 PLEASE SEE MANY NOTES FROM REVIEWS ONE
 AND TWO STILL NEED TO BE ADDRESSED.
  
 1)NOTE:PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL
 SCHEDULE(S).
 PLEASE SEE THERE ARE A FEW ITEMS ON
 PLANS WHICH STILL DO NOT SHOW THE
 CIRCUITING.
 PLEASE ALSO SEE NEW WATER FOUNTAIN HAS
 BEEN ADDED TO PLANS , HOWEVER PLANS DO
 NOT INDICATE ANY ELECTRICAL RECEPT FOR
 THIS UNIT.
  
 2) PLEASE SEE 700.12E FOR EM/EXT LTS.
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 215.5
  
 3)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE SEE LOAD CALCULATIONS SUBMITTED
 ARE ONLY LOAD ON SUB PANEL.
 PLEASE SHOW LOAD CALCUALTIONS FOR
 SERVICE AS REQUESTED ON PREVIOUS
 REVIEWS. PLEASE ALSO
 SEE LOAD CALCULATIONS ARE FOR
 RESIDENTIAL USE.
  
 4)NOTE: PLEASE SEE NEW MAIN DISCONNECT
 PANELS APPEARS TO BE SHOWN, HOWEVER NO
 INFORMATION IS PROVIDED FOR THIS.
 AIC RATING, VOLTAGE, AMPERAGE, GROUPING
 ETC
 215.5,110.9,110.14,230.72 ETC
 PLEASE SHOW PANELS, SERVICE LOCATION ON
 PLANS.
 PLEASE INDICATE CONDUCTORS FROM METER TO
 MAIN AND MAIN TO NEW SUB PANEL.
 215.5,240.4,310.16,250.24,250.6 ETC.
 ** PLEASE KNOW, SINCE LOAD CALCUALTIONS
 HAVE STILL NOT BEEN SUBMITTED FOR
 SERVICE, REVIEW FOR EXISTING SERVICE ENT CONDUCTORS CAN
 NOT BE VERIFIED AT THIS
 TIME.
 ** PLEASE SEE AHU IS NOW BEING SHOWN AT
 125%, HOWEVR THIS IS NOT REQUIRED.
 PLEASE SEE 424.3B ONLY REQUIRES THE OCP
 TO BE SIZED AT 125%.
  
 5)NOTE: PLEASE SEE FLORIDA STATUES
 481.221 WHICH REQUIRES TO THE ARCHITECT
 TO ALSO DATE PLANS WHEN SIGNING AND
 SEALING SAID PLANS.
  
 6)NOTE: PLEASE SEE RISER NOW SHOWS NEW
 PANELS WHICH INDICATE THESE ARE FOR
 ADDITION??
 PLEASE VEIRFY IF THESE ARE EXISITNG, NEW
 ETC.
 PLEASE KNOW, THERE IS NOT ENOUGH
 INFORMATION FOR THESE PANELS AS THEY DO
 NOT APPEAR TO BE SHOWN ON PLANS.
 215.5
  
 7)NOTE: PLEASE SEE FLORIDA STATUES
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND PLANS WITH REPEAT
 COMMENTS THREE OR MORE TIME FOR THE SAME
 CODE COMPLIANCE COMMENT(S).
 PLEASE KNOW, AS REQUIRED PER ABOVE FS, A
 4X FEE FOR THE PLAN REVIEW PORTION OF
 THE PERMIT FEE SHALL BE ACCESSED TO THE
 "DESIGN PROFESSIONAL" FOR SAID
 VIOLATION.
 PLEASE SEE THE FEE OF $1,764.00 IS NOW
 ACCESSED AND IS REQUIRED PER FS
 553.80(2)(B) TO BE PAID BEFORE
 RE-SUBMITTING PLANS.
 ** PLEASE KNOW, ONE COPY OF EACH OF THE
 ELECTRICAL PLANS SUBMITTED ARE NOW BEING
 RETAINED FOR FILE AND POSSIBLE REVIEW BY
 THE STATE BOARD OF ARCHITECTS AND STATE
 OF FLORIDA'S LEGAL COUNSEL.
 ** PLEASE KNOW, IT IS STRONGLY SUGGESTED
 A MEETING BE HELD ONCE ALL REVIEWS ARE
 COMPLETED BEFORE RESUBMITTING PLANS FOR
 NEXT REVIEWTO GO OVER ANY COMMENTS OR
 QUESTIONS.
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETED SETS FOR
 REVIEW AND STAMPING.
 ONE COPY OF ALL OLD/VOIDED SHEETS SHALL
 BE SUBMITTED FOR REFERENCE.
 PLEASE SEE THE ABOVE WAS REQUESTED ON
 PREVIOUS REVIEW, HOWEVER ALL OLD/VOIDED
 SHEETS WERE LEFT IN SETS.
  
  
 PLEASESUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  