Date |
Text |
2005-07-22 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUBMING |
| FBC-2001 BUILDING |
| |
| A. THE PLANS HAVE BEEN CHANGED AND DO |
| NOT SHOW ANY FACILITIES REQUIRED BY |
| TABLE 403.1. NO RESPONSE TO FIRST REVIEW |
| COMMENTS. |
| 1. FELLOWSHIP HALL INDICATES 1,381SF |
| BEING ADDED TO EXISTING CHURCH AREA. |
| THIS WILL BE AN ASSEMBLY OCCUPANCY AND |
| AS SUCH WILL ADD 198 MORE OCCUPANTS TO |
| THE OCCUPANCY LOAD OF THE EXISTING |
| STRUCTURES. TABLE 1003.1 |
| 2. PER TABLE 403.1, 1 W/C FOR MEN AND 2 |
| W/C'S FOR WOMEN, 1 LAV FOR MEN, 2 LAVS |
| FOR WOMEN, A DRINKING FOUNTAIN AND A |
| SERVICE SINK ARE REQUIRED. |
| 3. SUBMIT A SANITARY AND A WATER RISER |
| DIAGRAM IN ISOMETRIC FORM FOR REVIEW. |
| SECTION 104.3.1.1. SHOW ALL PIPE SIZES, |
| VENTS ECT FOR SANT., AND ALL PIPE SIZES, |
| VALVES, RPZ BACKFLOW, WATER HAMMER |
| ARRESTORS, (WHERE REQUIRED BY SECTION |
| 604.9 LOCATED NEAR THE FIXTURE PER |
| PDI-WH 201) AND POINT OF CONNECTION TO |
| THE WATER SUPPLY. |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |