2005-07-06 00:00:00 | ************ UNSAT2ND REVIEW ********* |
| |
| PLEASE SEE SOME NOTES FROM PREVIOUS |
| REVIEW STILL NEED TO BE ADDRESSED. |
| |
| 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH PANEL |
| SCHEDULE(S). PLEASE SEE 700.12E FOR |
| EM/EXT LTS. |
| 215.5 |
| |
| 2)NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| PLEASE SHOW PER |
| 220.3,220.10,220.11,220.13 ETC. |
| PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| AT 125% PER 215.3,230.42 |
| PLEASE SEE LOAD CALCULATIONS SUBMITTED |
| ARE ONLY LOAD ON SUB PANEL. PLEASE ALSO |
| SEE LOAD CALCULATIONS ARE FOR |
| RESIDENTIAL USE. |
| |
| 2)NOTE: PLEASE SEE NEW MAIN DISCONNECT |
| APPEARS TO BE SHOWN, HOWEVER NO |
| INFORMATION IS PROVIDED FOR THIS. |
| AIC RATING, VOLTAGE, AMPERAGE, GROUPING |
| ETC |
| 215.5,110.9,110.14,230.72 ETC |
| PLEASE INDICATE CONDUCTORS FROM METER TO |
| MAIN AND MAIN TO NEW SUB PANEL. |
| 215.5,240.4,310.16,250.24,250.6 ETC. |
| |
| 3)NOTE: PLEASE SHOW LOCATION OF COND |
| UNIT AND DISC'S REQUIRED FOR A/C CU AND |
| AHU. 440.11 |
| PLEASE ALSO SEE MISSING GFI RECEPT FOR |
| CU. 210.63 |
| |
| PLEASE BE SURE TO SEE ANY POSSIBLE |
| COMMENTS FROM OTHER REVIEWER(S) WHICH |
| MAY AFFECT ELECTRICAL PLANS. |
| |
| PLEASE REMOVE ANY AND ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| STAMPING. |
| |
| PLEASESUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |