Plan Review Notes
Plan Review Notes For Permit 05010378
Permit Number 05010378
Review Stop B
Sequence Number 2
Notes
Date Text
2005-07-24 00:00:00PERMIT: 05010378
 ADD: 909 3RD ST
 CONT: NEWBOLD CONSTRUCTION
 TEL: (561)644-5764
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 THE NOC FILED WILL HAVE THE WRONG
 PROPERTY CONTROL NUMBER ONCE THE UNITY
 OF TITLE OCCURS.WILL HAVE TO BE REFILED.
  
  
 2) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC TABLE 600
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.SEE ATTACHMENTS. UNITY OF
 TITLE FORMS ARE FOUND ON THE 5TH FLOOR
 ZONING DEPARTMENT.
  
 3 PROVIDE WHAT SLOPE THE CRICKET WILL
 HAVE? WILL IT ALSO HAVE SHINGLES ON
 ROOF?
  
 4) PROVIDE THE POSITIVE AND NEGATIVE
 PRESSUESFOR OPENINGS ON ELEVATIONS,
 ENCLUDE ENDZONES.
  
 5)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS
 B) ROOFING ASSEMBLIES
 C) TRACO WINDOWS DADE COUTY REPORT
 SUBMITTED SHOULD BE AAMA CERTIFICATION
 PROGRAM.
 D) STORM SHUTTERS REPORT SUBMITTED IS A
 SBCCI REPORT SUBMITTED TO STATE IS A
 MIAMI/ DADE REPORT CORRECT.
  
 7) FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 8) SHEET 5 NOW IS MISSING?
  
 9) IS THE STEEPLE PART OF THIS PERMIT?
  
 10) SHEET 2 MISSING THE EXITFROM THE
 DINING ROOM INTO THE FELLOWSHIP HALL.
 FROM THE EXISTING ROOM CONNECTING WITH
 THE PROPOSED FELLOWSHIP HALL ONLY HAS
 ONE EXIT INTO THE NEW FELLOWSHIP HALL,
 2 EXITS ARE REQUIRED FOR ROOMS WITH
 OCCUPANT LOADS GREATER THAN 50.
 1004.1.4 WHERE 2 OR MORE EXITS OR
 EXIT ACCESS DOORS ARE REQUIED, AT LEAST
 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL
 BE PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN 1/2 OF THE LENGTH OF THE MAX-
 IMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED.
  
 EXIT SIGNS SHALL BE MARKED BY AN
 APPROVED SIGN READILY VISIBLE FROM ANY
 DIRECTION OF EXIT ACCESS. EVERY EXIT
 SIGN SHALL BE SUITABLE ILLUMINATED BY A
 RELIABLE LIGHT SOURCE. EXTERNALLY AND
 INTERNALLY ILLUMINATED SIGNS SHALL BE
 VISIBLE IN BOTH THE NORMAL & EMERGENCY
 LIGHTING.MISSING IN EXISTING FELLOWSHIP
 HALL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026