2005-01-20 00:00:00 | ************** UNSAT *************** |
| |
| 1)NOTE: PLEASE SEE PLANS AREMISSING |
| REQUIRED TITLE BLOCKS WITH ALL REQUIRED |
| INFORMATION AS SET-FORTH IN FAC |
| 61G15-23.002 AND FS 471.023. |
| THIS IS REQUIRED ON ALL PLANS AND FOR |
| ALL SHEETS WHEATHER OR NOT COMMENT IS |
| MADE BY OTHER REVIEWER(S). |
| |
| 2)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH SUBMITTED PANEL |
| SCHEDULE(S). |
| PLEASE ALSO SEE 700.12E FOR CIRCUITING |
| OF EM/EXT LTS. |
| |
| 3)NOTE: PLEASE CORRELATE ALL A/C |
| EAUIPMENT AND LOADS ON PANEL, RISER AND |
| LOAD CALCULATIONS. |
| 215.5 |
| |
| 4)NOTE: PLEASE SEE 424.3B FOR SIZING OF |
| OCP.THE AMPACITY OF THE BRANCH-CIRCUIT |
| CONDUCTORS AND THE RATING OR SETTING OF |
| OVERCURRENT PROTECTIVE DEVICES SUPPLYING |
| FIXED ELECTRIC SPACE-HEATING EQUIPMENT |
| CONSISTING OF RESISTANCE ELEMENTS WITH |
| OR WITHOUT A MOTOR SHALL NOT BE LESS |
| THAN 125 PERCENT OF THE TOTAL LOAD OF |
| THE MOTORS AND THE HEATERS. THE RATING |
| OR SETTING OF OVERCURRENT PROTECTIVE |
| DEVICES SHALL BE PERMITTED IN ACCORDANCE |
| WITH 240.4(B). |
| |
| 5)NOTE: PLEASE VERIFY SIZE OF SEC'S, |
| SHOWS 200A MCB PANEL WITH ONE PHASE DOWN |
| SIZED? HOW IS THIS CONDUCTOR PROTECTED? |
| 240.4 |
| PLEASE SEE RISER INDICATES 3-PHASE YET, |
| THIS IS NOT SHOWN ON CALCS? |
| PLEASE SEE LOAD IS SHOWN AT 216A'S ON A |
| 200A PANEL. |
| |
| |
| 6)NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| PLEASE SHOW PER |
| 220.3,220.10,220.11,220.13 ETC. |
| PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| AT 125% PER 215.3,230.42 |
| |
| 7)NOTE: PLEASE SEE 422.13 A BRANCH |
| CIRCUIT SUPPLYING A FIXED STORAGE-TYPE |
| WATER HEATER THAT HAS A CAPACITY OF 450 |
| L (120 GAL) OR LESS SHALL HAVE A RATING |
| NOT LESS THAN 125 PERCENT OF THE |
| NAMEPLATE RATING OF THE WATER HEATER. |
| PLEASE SEE MAX OCP IS 150% 422.11E |
| IF THE OVERCURRENT PROTECTION RATING IS |
| NOT MARKED AND THE APPLIANCE IS RATED |
| OVER 13.3 AMPERES, NOT EXCEED 150 |
| PERCENT OF THE APPLIANCE RATED CURRENT. |
| WHERE 150 PERCENT OF THE APPLIANCE |
| RATING DOES NOT CORRESPOND TO A STANDARD |
| OVERCURRENT DEVICE AMPERE RATING, THE |
| NEXT HIGHER STANDARD RATING SHALL BE |
| PERMITTED. |
| |
| PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| OTHER REVIEWER(S) WHICH MAY AFFECT |
| ELECTRICAL PLANS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO TWO |
| COMPLETE SETSFOR REVIEW AND STAMPING. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |