2005-01-20 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE SEE PLANS AREMISSING
 REQUIRED TITLE BLOCKS WITH ALL REQUIRED
 INFORMATION AS SET-FORTH IN FAC
 61G15-23.002 AND FS 471.023.
 THIS IS REQUIRED ON ALL PLANS AND FOR
 ALL SHEETS WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED PANEL
 SCHEDULE(S).
 PLEASE ALSO SEE 700.12E FOR CIRCUITING
 OF EM/EXT LTS.
  
 3)NOTE: PLEASE CORRELATE ALL A/C
 EAUIPMENT AND LOADS ON PANEL, RISER AND
 LOAD CALCULATIONS.
 215.5
  
 4)NOTE: PLEASE SEE 424.3B FOR SIZING OF
 OCP.THE AMPACITY OF THE BRANCH-CIRCUIT
 CONDUCTORS AND THE RATING OR SETTING OF
 OVERCURRENT PROTECTIVE DEVICES SUPPLYING
 FIXED ELECTRIC SPACE-HEATING EQUIPMENT
 CONSISTING OF RESISTANCE ELEMENTS WITH
 OR WITHOUT A MOTOR SHALL NOT BE LESS
 THAN 125 PERCENT OF THE TOTAL LOAD OF
 THE MOTORS AND THE HEATERS. THE RATING
 OR SETTING OF OVERCURRENT PROTECTIVE
 DEVICES SHALL BE PERMITTED IN ACCORDANCE
 WITH 240.4(B).
  
 5)NOTE: PLEASE VERIFY SIZE OF SEC'S,
 SHOWS 200A MCB PANEL WITH ONE PHASE DOWN
 SIZED? HOW IS THIS CONDUCTOR PROTECTED?
 240.4
 PLEASE SEE RISER INDICATES 3-PHASE YET,
 THIS IS NOT SHOWN ON CALCS?
 PLEASE SEE LOAD IS SHOWN AT 216A'S ON A
 200A PANEL.
  
  
 6)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 7)NOTE: PLEASE SEE 422.13 A BRANCH
 CIRCUIT SUPPLYING A FIXED STORAGE-TYPE
 WATER HEATER THAT HAS A CAPACITY OF 450
 L (120 GAL) OR LESS SHALL HAVE A RATING
 NOT LESS THAN 125 PERCENT OF THE
 NAMEPLATE RATING OF THE WATER HEATER.
 PLEASE SEE MAX OCP IS 150% 422.11E
 IF THE OVERCURRENT PROTECTION RATING IS
 NOT MARKED AND THE APPLIANCE IS RATED
 OVER 13.3 AMPERES, NOT EXCEED 150
 PERCENT OF THE APPLIANCE RATED CURRENT.
 WHERE 150 PERCENT OF THE APPLIANCE
 RATING DOES NOT CORRESPOND TO A STANDARD
 OVERCURRENT DEVICE AMPERE RATING, THE
 NEXT HIGHER STANDARD RATING SHALL BE
 PERMITTED.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETSFOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]