2005-01-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05010378
 ADD: 909 3RD ST
 CONT: NEWBOLD CONSTRUCTION
 TEL: (561)644-5764
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC TABLE 600
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
  
 3) 3401.7.1.1.2 WHEN THE ADDITION IS
 OVER 25% OF THETHE EXISTING BUILDING
 AREA AND NOT SEPERATED BY A FIRE WALL,
 THE EXISTING BUILDING AND THE ADDITION
 SHALL BE MADE TO COMPLY WITH ALL THE
 REQUIREMENTS OF THIS CODE FOR A BUILDING
 OF AREA EQUAL TO THE COMBINED AREA OF
 THE ADDITION AND EXISTING BUILDING.
 EXCEP: EXISTING BUILDINGS SHALL NOT BE
 REQUIRED TO BE UPGRADED TO THE
 STRUCTURAL REQUIREMENTS OF THE CODE IN
 EFFECT ON THE DATE OF THE PERMIT FOR THE
 ADDTION.
 4) PROVIDE THE CORRECT ENERGY FORMS, THE
 FORM SUBMITTED IS FOR RESIDENTIAL USE.
  
 5) DESIGN STANARDS TO BE REVISED AND
 UPDATED:
 2001 FLORIDA BUILDING CODE W/ 2003
 REVISIONS
 CONCRETE ACI 318-02
 MASONARY ACI 530/ ASCE 5 TMS402-02
  
 6) GABLE ENDWALL PLANS INDICATE THE USE
 OF A GABLE BEAM BUT NO MENTION OF THE
 BEAM AT THE EAVE HEIGHT NOR USE OF
 LENTALS? WHAT WILL HAPPEN OVER THE DOOR
 AND WINDOW OPENINGS?
  
 7) NO INFORMATION FOR WINDOW AND DOOR
 SIZES?
  
 8) PROVIDE WHAT SLOPE THE NEW ADDITION
 ROOF WILL BE?
  
 9) PROVIDE THE POSITIVE AND NEGATIVE
 PRESSUESFOR OPENINGS ON ELEVATIONS,
 ENCLUDE ENDZONES.
  
 10) FRONT ELEVATION OF THE FELLOWSHIP
 HALL MISSING THE 16" BEAM ON THE
 ELEVATION?
  
 11)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 12)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS
 B) ROOFING ASSEMBLIES
  
 13) WINDOW BUCK DETAIL INDICATES THE
 USE OF A 1X2 BUCK WINDOW FRAME IS A
 2.25" WIDE. 1707.4.4.2 TAPERED
 BUCKS: SHALL EXTEND BEYOND THE INTERIOR
 FACE OF THE WINDOW OR DOOR FRAME SUCH
 THAT FULL SUPPORT OF THE FRAME IS
 SUPPORTED.
  
 14) FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 15) SHEET 5 INDICATES THE USE OF A 90LB
 FELT FOR DRY IN??
  
 16) IS THE STEEPLE PART OF THIS PERMIT?
  
 17) SHEET 2 MISSING THE EXITFROM THE
 DINING ROOM INTO THE FELLOWSHIP HALL.
 1016.3.1. EXIT SIGNS:
 EXIT SIGNS SHALL BE MARKED BY AN
 APPROVED SIGN READILY VISIBLE FROM ANY
 DIRECTION OF EXIT ACCESS. EVERY EXIT
 SIGN SHALL BE SUITABLE ILLUMINATED BY A
 RELIABLE LIGHT SOURCE. EXTERNALLY AND
 INTERNALLY ILLUMINATED SIGNS SHALL BE
 VISIBLE IN BOTH THE NORMAL & EMERGENCY
 LIGHTING.
  
 BUILDING PLAN REVIEW