2005-01-24 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 05010378 |
| ADD: 909 3RD ST |
| CONT: NEWBOLD CONSTRUCTION |
| TEL: (561)644-5764 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 1) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2) THE PROPOSED BUILDING STRUCTURE |
| TRANSGRESSES LEGAL BOUNDARY LINES |
| BETWEEN THE LOTS WHICH COMBINE TO FORM |
| 'THE SITE'.A 'UNITY OF TITLE' SHALL BE |
| RECORDED AT THE COUNTY COURTHOUSE. |
| SUBMIT A COPY OF THE RECORDED 'UNITY OF |
| OF TITLE' DOCUMENT SO THAT FBC TABLE 600 |
| BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| NOT APPLICABLE. |
| |
| 3) 3401.7.1.1.2 WHEN THE ADDITION IS |
| OVER 25% OF THETHE EXISTING BUILDING |
| AREA AND NOT SEPERATED BY A FIRE WALL, |
| THE EXISTING BUILDING AND THE ADDITION |
| SHALL BE MADE TO COMPLY WITH ALL THE |
| REQUIREMENTS OF THIS CODE FOR A BUILDING |
| OF AREA EQUAL TO THE COMBINED AREA OF |
| THE ADDITION AND EXISTING BUILDING. |
| EXCEP: EXISTING BUILDINGS SHALL NOT BE |
| REQUIRED TO BE UPGRADED TO THE |
| STRUCTURAL REQUIREMENTS OF THE CODE IN |
| EFFECT ON THE DATE OF THE PERMIT FOR THE |
| ADDTION. |
| 4) PROVIDE THE CORRECT ENERGY FORMS, THE |
| FORM SUBMITTED IS FOR RESIDENTIAL USE. |
| |
| 5) DESIGN STANARDS TO BE REVISED AND |
| UPDATED: |
| 2001 FLORIDA BUILDING CODE W/ 2003 |
| REVISIONS |
| CONCRETE ACI 318-02 |
| MASONARY ACI 530/ ASCE 5 TMS402-02 |
| |
| 6) GABLE ENDWALL PLANS INDICATE THE USE |
| OF A GABLE BEAM BUT NO MENTION OF THE |
| BEAM AT THE EAVE HEIGHT NOR USE OF |
| LENTALS? WHAT WILL HAPPEN OVER THE DOOR |
| AND WINDOW OPENINGS? |
| |
| 7) NO INFORMATION FOR WINDOW AND DOOR |
| SIZES? |
| |
| 8) PROVIDE WHAT SLOPE THE NEW ADDITION |
| ROOF WILL BE? |
| |
| 9) PROVIDE THE POSITIVE AND NEGATIVE |
| PRESSUESFOR OPENINGS ON ELEVATIONS, |
| ENCLUDE ENDZONES. |
| |
| 10) FRONT ELEVATION OF THE FELLOWSHIP |
| HALL MISSING THE 16" BEAM ON THE |
| ELEVATION? |
| |
| 11)PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 12)FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) TRUSS ANCHORS |
| B) ROOFING ASSEMBLIES |
| |
| 13) WINDOW BUCK DETAIL INDICATES THE |
| USE OF A 1X2 BUCK WINDOW FRAME IS A |
| 2.25" WIDE. 1707.4.4.2 TAPERED |
| BUCKS: SHALL EXTEND BEYOND THE INTERIOR |
| FACE OF THE WINDOW OR DOOR FRAME SUCH |
| THAT FULL SUPPORT OF THE FRAME IS |
| SUPPORTED. |
| |
| 14) FL BLD CODE 2001 SECTION 103.6, |
| 1606.1.4, 1707.4 & 3401.7.2.4. |
| PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| SCHEDULE SUMMARIZING & IDENTIFYING |
| OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| BAR REINFORCING REQUIREMENTS, WALL PRES- |
| SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| SUBMITTED AT TIME OF PERMIT APPLICATION |
| TO FACILITATE PLAN REVIEW AND PERMIT |
| ISSUANCE. |
| |
| 15) SHEET 5 INDICATES THE USE OF A 90LB |
| FELT FOR DRY IN?? |
| |
| 16) IS THE STEEPLE PART OF THIS PERMIT? |
| |
| 17) SHEET 2 MISSING THE EXITFROM THE |
| DINING ROOM INTO THE FELLOWSHIP HALL. |
| 1016.3.1. EXIT SIGNS: |
| EXIT SIGNS SHALL BE MARKED BY AN |
| APPROVED SIGN READILY VISIBLE FROM ANY |
| DIRECTION OF EXIT ACCESS. EVERY EXIT |
| SIGN SHALL BE SUITABLE ILLUMINATED BY A |
| RELIABLE LIGHT SOURCE. EXTERNALLY AND |
| INTERNALLY ILLUMINATED SIGNS SHALL BE |
| VISIBLE IN BOTH THE NORMAL & EMERGENCY |
| LIGHTING. |
| |