Plan Review Notes For Permit 05010365 |
Permit Number |
05010365 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2005-05-19 00:00:00 | PROVISO: | | 1.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | REQUIRED WITH NOTIFICATION TO | | ALARM/STROBE IN NORMALLY OCCUPIED AREAS. | | | | 2.THE LOCATION OF THE ACCU-1 APPEARS | | TO BE "INSIDE".CONDENSOR UNITS ARE TO | | BE INSTALLED "OUTSIDE" (OUTDOORS) PER | | THE MANUFACTURER'S SPECIFICATIONS. | | PLEASE REVISE PLANS TO RE-LOCATE ACCU-1. | | | | PER 2001 FBC CHAPTER 13 SUB SECTION | | 407.1.ABCD.3.3, THE CONDENSING COIL OF | | ONE AIR CONDITIONING UNIT SHALL NOT BE | | INSTALLED IN THE COOL AIR STREAM OF | | ANOTHER AIR CONDITIONING UNIT. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|