Plan Review Notes
Plan Review Notes For Permit 05010365
Permit Number 05010365
Review Stop M
Sequence Number 3
Notes
Date Text
2005-05-19 00:00:00PROVISO:
 1.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 REQUIRED WITH NOTIFICATION TO
 ALARM/STROBE IN NORMALLY OCCUPIED AREAS.
  
 2.THE LOCATION OF THE ACCU-1 APPEARS
 TO BE "INSIDE".CONDENSOR UNITS ARE TO
 BE INSTALLED "OUTSIDE" (OUTDOORS) PER
 THE MANUFACTURER'S SPECIFICATIONS.
 PLEASE REVISE PLANS TO RE-LOCATE ACCU-1.
  
 PER 2001 FBC CHAPTER 13 SUB SECTION
 407.1.ABCD.3.3, THE CONDENSING COIL OF
 ONE AIR CONDITIONING UNIT SHALL NOT BE
 INSTALLED IN THE COOL AIR STREAM OF
 ANOTHER AIR CONDITIONING UNIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.