Plan Review Notes
Plan Review Notes For Permit 05010365
Permit Number 05010365
Review Stop P
Sequence Number 2
Notes
Date Text
2005-03-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A) FOLLOWING COMMENTS WERE NOT ADDRESSED
 OR NOT ADDRESSED SUFFICIENTLY. THE
 COMMENT NUMBER SHALL STAY THE SAME TO
 AVOID CONFUSION.
 1) SHTS IRR 1,2,&3 PRINTED NAME OF THE
 PERSON SEALING THE PLANS IS REQURED ON
 THE TITLE BLOCK. FAC 61G1-16.004(6) & FS
 481.2055. RESPONSE NOTED "OUR DOCUMENTS
 DO NOT INCLUDE AN IRR SHEET SERIES".
 THERE ARE IRRIGATION SHEETS SUBMITTED.
 ALSO THE CERTIFICATE OF AUTHORIZTION IS
 REQUIRED FOR ALL IRR. SHEETS. THIS IS
 REQUIRED AS AN "AA" OR "AR" NUMBER AS
 THE SHEETS WERE SIGNED & SEALED BY A
 LANDSCAPE ARCHITECT. FS 481.219(2)
 3) OIL WATER SEPARATOR SHALL BE SIZED
 AND APPROVED BY RODNEY COMPO,
 ENVIRONMENTAL COMPLIANCE. WASTE ORD
 #2938-96. (561) 837-4074 - RESPONSE
 NOTED, BUT SEE ATTACHED SHEET FROM
 RODNEY COMPO REQUIREING A 100 GAL OIL
 WATER SEPARATOR. SEPARATE PERMIT
 REQUIRED FOR SEPARATOR.
 10) ALL SHEETS, TITLE BLOCK FOR
 ARCHITECT, THE COMPANY NAME IS NOT THE
 SAME AS SHOWN ON THE DBPR LICENSE SEARCH
 FOR THE CERTIFICATE OF AUTHORIZATION,
 PLEASE MAKE THE CORRECTION ON THE TITLE
 BLOCK, SHOW APPROIATE BUSINESS NAME.
 (SEE ATTACHED SHEET FROM DBPR WEBSITE).
 FAC 61G1-16.004 & FS 481.291 - ALL
 SHEETS FOR ARCHITECT AND ENGINEER, THE
 DATE THAT THE SEAL AND SIGNATURE IS
 AFFIXED SHALL BE ON THE SEAL. FAC
 61G15-23.002(2) - FAC 61G1-16.003 / FS
 471.025 - 481.2055.
 11) SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES FOR FIXTURES. 2 DRINKING
 FOUNTAINS ARE REQUIRED. SHT TO-1
 INDICATES A DRINKING FOUNTAIN IN LOBBY
 AREA, BUT NO DRINKING FOUNTAIN IS SHOWN
 ON THE FLOOR PLAN, NOR ON THE SANT. OR
 WATER PIPING RISERS. ONLY ONE WATER
 COOLER IS SHOWN.
 13) SHT PE.1 WATER RISER ISOMETRIC SHALL
 SHOW FULL OPEN VALVES ON ALL EVER WATER
 DOWN-FEED WATER LINE. SECTION 606.1(4)
 ALL WATER HAMMER ARRESTORS SHALL BE
 LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 & MANUF. INSTALL.
 INSTRUCTIONS.
 15) A SEPARATE GAS PERMIT IS REQUIRED,
 AND THE FOLLOWING INFORMATION IS
 REQUIRED TO ISSUE THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. - NOT ALL LENGTHS ARE
 SHOWN ON THE ISOMETRIC. SHOW LOCATION OF
 METER AND ALL MEASURMENTS TO METER.
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). - THIS WAS
 NOT SHOWN ON THE PLANS.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. -
 IF THE GAS DELIVERY PRESSURE IS .5 PSI,
 DELETE ALL SECONDARY REGULATORS FROM THE
 ISOMETRIC AS THEY WILL NOT BE IN SYSTEM.
 ALL SHUT OFF VALVES SHALL BE LOCATE
 MAXIMUM OF 6' FROM GAS APPLIANCE.
 SECTION 409.7. SOME ARE SHOWN EXCEEDING
 THIS REQUIREMENT ON THE ISOMETRIC.
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2. - NO
 SHEETS WERE FOUND.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.-
 THE SHEETS THAT WERE VOIDED WERE NOT
 REMOVED FROM THE SETS OF PLANS. REMOVE
 ALL OLD SHEET AND SUBMIT ONE SET OF OLD
 SHEETS FOR COMPARISON. - ONE SET OF
 PLANS SUBMITTED FOR REVIEW WAS SUBMITTED
 AS LOOSE SHEETS. PLEASE SUBMIT TWO OR
 MORE SETS OF PLANS FOR REVIEW. SECTION
 104.2.1.
 **************NEW COMMENT***************
 1B) THE FOLLOWING SHEETS ARE NOT SHOWN
 ON THE DRAWING INDEX, BUT WERE INCLUDED
 IN THE SETS OF PLANS. SHEETS 1 THRU 11
 OF 11, SHEET 1 OF 1, L1 & L2, IRR 1,2,3
 PH-1, E1 OF 2, E1 OF 6. CORRELATE THE
 INDEX SHEET WITH SHEETS SUBMITTED.
 SECTION 104.2.1.