Date |
Text |
2005-03-08 00:00:00 | ********* UNSAT 2ND REVIEW ********* |
| |
| PLEASE SEE PLANS ARE STILL ONLY IN FOR |
| PLAN REVIEW AND HAVE NOT BEEN SUBMITTED |
| FOR PERMIT. |
| |
| |
| PLEASE SEE SOME NOTES FROM FIRST REVIEW |
| STILL NEED TO BE ADDRESSED. |
| |
| 1)NOTE: NOTE #1 NO, PLEASE INCLUDE ALL |
| REQUIRED LICENSE INFORMATION ON TITLE |
| BLOCKS FOR ALL TRADES AND FOR ALL SHEETS |
| AS REQUIRED UNDER FS 481.219,471.023 |
| FAC 61G1-16.004,61G15-23.002. |
| PLEASE SEE ATTACHED SHEETS FROM STATE |
| DBPR SITE PERTAINING TO FIRM SHOWN ON |
| PLANS. |
| THIS FIRM IS SHOWN AS "APPLICANT" AT |
| THIS TIME. |
| PLEASE SEE ALL TITLE BLOCKS. PH-SHEETS |
| ETC. |
| PLEASE ALSO BE AWARE, FIRM # SHOWN ON |
| PLANS AT THIS TIME APPEAR TO BELONG TO A |
| DIFFERENT FIRM. |
| PLEASE ALSO BE AWARE, FIRM NAME AS |
| REGISTERED WITH STATE MUST BE THE SAME |
| AS ON TITLE BLOCK. |
| PLEASE SEE THIS IS REQUIRED OF ALL |
| SHEETS AND TRADES WHEATHER OR NOT |
| COMMENT IS MADE BY OTHER REVIEWER(S). |
| |
| 2)NOTE: NOTE #2, NO, PLEASE SEE SOME |
| SHEETS SEAL IS NOT CLEARLY VISABLE WITH |
| INFORMATION REQUIRED. PLEASE SEE FS |
| 471.025 FOR ENGINEERS AND 481.221 FOR |
| ARCH'S. |
| PLEASE ALSO SEE PLANS MUST BE SIGNED, |
| "DATED " AND SEALED. |
| LTR FROM ENGINEER MR. JAMES FOX WAS |
| RECIEVED AND PLACED IN FILE FOR |
| SIGNATURE VERIFICATION. |
| |
| 3)NOTE:NOTE #3, OK, BLDG TO REVIEW WIND |
| LOAD CALCULATIONS. |
| |
| 4)NOTE: NOTE #4 NO, PLEASE SEE CWP AND |
| GRND ROD WAS ADDED, HOWEVER FOOTER |
| STEEL, WAS NOT SHOWN. PLEASE SEE PLANS |
| REFERENCE 250.50 FOR GES. PLEASE SEE FBC |
| 104.2.1, PLANS SHALL NOT CONTAIN |
| REFERENCE TO TECHNICAL CODES IN WHOLE OR |
| IN PART. |
| |
| 5)NOTE: NOTE #5, OK, NOT SHOWN PER |
| DETAIL NEC ARTICLES, HOWEVER ALL LOADS |
| ARE SHOWN AS CONNECTED LOAD W/OUT |
| DERATING. THIS IS OK. |
| |
| 6)NOTE: NOTE #6, NO, PLEASE SEE PREVIOUS |
| COMMENT WAS NOT TO CHANGE IDENTIFICATION |
| OF MDP TO MCB. IT WAS TO REQUIRE A MCB, |
| (MAIN CIRCUIT BREAKER). |
| PLEASE SEE MAIN IS SHOWN AS PART OF A |
| PANEL BOARD FOR SERVICE WHICH WILL |
| CONTAIN MORE THAN 6-SPACES FOR MEANS OF |
| DISC OF SERVICE. PLEASE SEE THAT A MCB |
| WILL BE REQUIRED.230.71A, 240.4 |
| |
| |
| 7)NOTE: NOTE #7 OK. |
| |
| |
| PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| REVIEWER(S) WHICH MAY AFFECT ELECTRICLA |
| PLANS. |
| |
| PLEASE REMOVE ALL OLD SHEETS AND INSERT |
| NEW REVISED SHEETS INTO COMPLETE SETS |
| FOR REVIEW AND STAMPING. |
| PLEASE SEE ALL SHEETS WERE LOOSE IN |
| ROLLS? |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |