Date |
Text |
2005-02-03 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FBC-2001 BUILDING |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1) SHTS IRR 1, 2, & 3 PRINTED NAME OF |
| THE OF THE PERSON SEALING THE PLANS IS |
| REQUIRED ON THE TITLE BLOCK. FAC |
| 61G1-16.004(6) & FS 481.2055 |
| 2) SHT IRR 3 POINT OF CONNECTION, |
| (POC), |
| STATES 2" WATER METER. CIVIL SHEET 8 OF |
| 11 INDICATES 1" TAP. PLEASE CLARIFY. |
| SECTION 104.2.1. |
| 3) OIL WATER SEPARATOR SHALL BE SIZED |
| AND APPROVED BY RODNEY COMPO, |
| ENVIRONMENTAL COMPLIANCE. WASTE ORD. |
| NO. |
| 2938-96. (561)837-4074. |
| 4) SHTS F1.1 & A8.2 CLEAR FLOOR SPACE |
| FOR WATER CLOSETS AND URINAL ARE |
| REQUIRED IN THE MENS TOILET ROOM. ALSO |
| SHOW THE TURNING ARE IN THE TOILET ROOM |
| NOT THE ACCESSIBLE STALL. - CLEAR FLOOR |
| SPACE FOR THE WATER CLOSET IS REQUIRED |
| IN THE WOMENS TOILET ROOM, WITH THE |
| TURNING AREA SHOWN IN THE TOILET ROOM |
| NOT THE ACCESSIBLE STALL. SECTIONS |
| 11-4.16.2, 11-4.18.3 & 11-4.22.3- |
| ALSO |
| SHOW THE CLEAR FLOOR SPACE FOR THE W/C |
| IN ROOM #106, THE CLEAR FLOOR SPACE FOR |
| THE BREAK ROOM SINK IN ROOM #115, |
| (FORWARD APPROACH IS REQUIRED - MAX. |
| 19" |
| UNDERNEATH THE SINK), 11-4.24.5. |
| 5) SHTS F1.1 & A8.2 BREAK ROOM SINK |
| MODEL #CR-25-21 INDICATES A 7" DEEP |
| SINK, BUT SECTION 11-4.24.4 STATES THAT |
| 6-1/2" IS THE MAXIMUM DEPTH. ALSO |
| FAUCET |
| SHALL BE LEVER OPERATED, PUSH TYPE, |
| TOUCH TYPE, OR ELECTRONICALLY |
| CONTROLLED. SECTION 11-4.24.7 |
| 6) SHT A1.2 ROOM FINISH SCHEDULE, MORE |
| INFORMATION FOR WB-1 & WB-2 SHOWN FOR |
| THE BASE. INDICATE MATERIAL TYPE. PER |
| SECTION 1204.2 MATERIAL SHALL BE NOT |
| ABSORBENT. PLEASE CLARIFY. |
| 7) SHT A1.2 ROOM FINISH NOTE #3. |
| INDICATE THAT WAINSCOT IS REQUIRED. |
| SECTION 104.2.1. & SECTION 1204.2. |
| 8) SHT A2.1 SUBMIT CALCULATIONS FOR |
| ROOF |
| DRAINS PER SECTIONS 1106 & 1107 AND ALL |
| SUBSECTIONS. SHOW TOTAL AREA OF THE |
| ROOF |
| AND SHOW 1/2 AREA OF ALL VERTICAL WALLS |
| INCLUDING PARAPETS. INDICATE THE AREA |
| OF |
| THE ROOF THAT DRAINS TO EACH DOWNSPOUT. |
| SHOW SIZE OF GUTTERS PER TABLE 1106.6, |
| INDICATE SLOPE OF GUTTERS AND SHOW THE |
| HIGH POINT OF THE GUTTER. |
| 9) SHT A8.1 DETAIL #2 SHOW KNEE |
| CLEARANCE 11-4.23.3, ACCESSIBLE WATER |
| CLOSET SHOW HEIGHT 11-4.16.3, |
| ACCESSIBLE |
| URINAL SHOW HEIGHT 11-4.18.2, CLEAR |
| FLOOR SPACE 11-4.18.3. |
| 10) ALL SHEETS, TITLE BLOCK FOR |
| ARCHITECT, THE COMPANY NAME IS NOT THE |
| SAME AS SHOWN ON DBPR LICENSE SEARCH |
| FOR |
| THE CERTIFICATE OF AUTHORIZATION. |
| PLEASE |
| MAKE THE CORRECTION ON THE TITLE BLOCK. |
| SHOW APPROIATE BUSINESS NAME. FAC |
| 61G1-16.004 & FS 481.291. - AN ENGINEER |
| SHALL SIGN HIS NAME AND AFFIX HIS SEAL |
| TO ALL PLANS. INITIALS ARE NOT |
| ACCEPTABLE. THE DATE THAT THE SIGNATURE |
| AND SEAL IS AFFIXED SHALL BE ENTERED ON |
| THE PLANS IMMEDIATELY UNDER THE |
| SIGNATURE OF THE PROFESSIONAL ENGINEER. |
| FAC 61G15-23.002(1) & FS 471.025 |
| 11) SUBMIT CALCULATIONS FOR MINIMUM |
| FACILITIES FOR FIXTURES. INDICATE ON |
| PLANS THE SQUARE FOOTAGE FOR EACH |
| OCCUPANCY. TABLES 1003.1 & 403.1. |
| 12) SHT P2.1 HOUSE TRAP NOT APPROVED. |
| DELETE FROM DETAIL "B". SECTION 1002.1 |
| 12) SHT P3.1 ALL RISER DIAGRAMS SHALL |
| BE |
| IN ISOMETRIC FORM AND SHALL REFLECT THE |
| FLOOR PLAN. SECTION 104.2.1. |
| 13) SHT P3.1 WATER RISER ISOMETRIC |
| SHALL |
| SHOW VALVES REQUIRED BY SECTION |
| 606.1(4) |
| FULL OPEN VALVES ON EVERY DOWN-FEED |
| WATER LINE, AND SHOW THE LOCATION OF |
| ALL |
| WATER HAMMER ARRESTORS REQUIRED BY |
| SECTION 604.9 AND SHALL BE LOCATED NEAR |
| THE FIXTURE, IN AN "EFFECTIVE RANGE" |
| NOT |
| IN THE CEILING AS SHOWN. PDI-WH 201 AND |
| MANUF. INSTALLATION INSTRUCTIONS. |
| 14) SHT P3.1 INSPECTION BAY WASTE & |
| VENT |
| INDICATES A VERTICAL VENT FOR THE 4" |
| FD-3 ON RISER DIAGRAM, BUT ON SHT P2.1 |
| THE VENT IS INDICATED AS A HORIZONTAL |
| DRY VENT WHICH IS NOT APPROVED PER |
| SECTION 905.3 & 905.4 PLEASE CLARIFY. |
| 15) A SEPARATE GAS PERMIT IS REQUIRED, |
| AND THE FOLLOWING INFORMATION IS |
| REQUIRED TO ISSUE THE GAS PERMIT: |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE IF BEING |
| USED. |
| C. TYPE OF GAS, (LP OR NATURAL) |
| D. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| THRU 402.5.2 AND TABLES 402(1) THRU |
| 402(34). |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM |
| PER |
| FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES (A)(3). |
| F. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| GAS CODE SECTION 304. |
| G. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| H. SUBMIT MANUFACTURE SHEETS FOR ALL |
| GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2001 FUEL GAS CODE SEC 402.2 |
| I. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY |
| LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, |
| BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| J. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK |
| AND |
| APPURTENANCES PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| K) INDICATE TYPE OF MATERIAL FOR |
| REGULATOR VENTS. VENT MATERIAL SHALL BE |
| NON COMBUSTABLE. SECTION 631.15 |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT |
| NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR |
| SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE |
| FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |