Plan Review Notes
Plan Review Notes For Permit 05010365
Permit Number 05010365
Review Stop P
Sequence Number 1
Notes
Date Text
2005-02-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHTS IRR 1, 2, & 3 PRINTED NAME OF
 THE OF THE PERSON SEALING THE PLANS IS
 REQUIRED ON THE TITLE BLOCK. FAC
 61G1-16.004(6) & FS 481.2055
 2) SHT IRR 3 POINT OF CONNECTION,
 (POC),
 STATES 2" WATER METER. CIVIL SHEET 8 OF
 11 INDICATES 1" TAP. PLEASE CLARIFY.
 SECTION 104.2.1.
 3) OIL WATER SEPARATOR SHALL BE SIZED
 AND APPROVED BY RODNEY COMPO,
 ENVIRONMENTAL COMPLIANCE. WASTE ORD.
 NO.
 2938-96. (561)837-4074.
 4) SHTS F1.1 & A8.2 CLEAR FLOOR SPACE
 FOR WATER CLOSETS AND URINAL ARE
 REQUIRED IN THE MENS TOILET ROOM. ALSO
 SHOW THE TURNING ARE IN THE TOILET ROOM
 NOT THE ACCESSIBLE STALL. - CLEAR FLOOR
 SPACE FOR THE WATER CLOSET IS REQUIRED
 IN THE WOMENS TOILET ROOM, WITH THE
 TURNING AREA SHOWN IN THE TOILET ROOM
 NOT THE ACCESSIBLE STALL. SECTIONS
 11-4.16.2, 11-4.18.3 & 11-4.22.3-
 ALSO
 SHOW THE CLEAR FLOOR SPACE FOR THE W/C
 IN ROOM #106, THE CLEAR FLOOR SPACE FOR
 THE BREAK ROOM SINK IN ROOM #115,
 (FORWARD APPROACH IS REQUIRED - MAX.
 19"
 UNDERNEATH THE SINK), 11-4.24.5.
 5) SHTS F1.1 & A8.2 BREAK ROOM SINK
 MODEL #CR-25-21 INDICATES A 7" DEEP
 SINK, BUT SECTION 11-4.24.4 STATES THAT
 6-1/2" IS THE MAXIMUM DEPTH. ALSO
 FAUCET
 SHALL BE LEVER OPERATED, PUSH TYPE,
 TOUCH TYPE, OR ELECTRONICALLY
 CONTROLLED. SECTION 11-4.24.7
 6) SHT A1.2 ROOM FINISH SCHEDULE, MORE
 INFORMATION FOR WB-1 & WB-2 SHOWN FOR
 THE BASE. INDICATE MATERIAL TYPE. PER
 SECTION 1204.2 MATERIAL SHALL BE NOT
 ABSORBENT. PLEASE CLARIFY.
 7) SHT A1.2 ROOM FINISH NOTE #3.
 INDICATE THAT WAINSCOT IS REQUIRED.
 SECTION 104.2.1. & SECTION 1204.2.
 8) SHT A2.1 SUBMIT CALCULATIONS FOR
 ROOF
 DRAINS PER SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. SHOW TOTAL AREA OF THE
 ROOF
 AND SHOW 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS. INDICATE THE AREA
 OF
 THE ROOF THAT DRAINS TO EACH DOWNSPOUT.
 SHOW SIZE OF GUTTERS PER TABLE 1106.6,
 INDICATE SLOPE OF GUTTERS AND SHOW THE
 HIGH POINT OF THE GUTTER.
 9) SHT A8.1 DETAIL #2 SHOW KNEE
 CLEARANCE 11-4.23.3, ACCESSIBLE WATER
 CLOSET SHOW HEIGHT 11-4.16.3,
 ACCESSIBLE
 URINAL SHOW HEIGHT 11-4.18.2, CLEAR
 FLOOR SPACE 11-4.18.3.
 10) ALL SHEETS, TITLE BLOCK FOR
 ARCHITECT, THE COMPANY NAME IS NOT THE
 SAME AS SHOWN ON DBPR LICENSE SEARCH
 FOR
 THE CERTIFICATE OF AUTHORIZATION.
 PLEASE
 MAKE THE CORRECTION ON THE TITLE BLOCK.
 SHOW APPROIATE BUSINESS NAME. FAC
 61G1-16.004 & FS 481.291. - AN ENGINEER
 SHALL SIGN HIS NAME AND AFFIX HIS SEAL
 TO ALL PLANS. INITIALS ARE NOT
 ACCEPTABLE. THE DATE THAT THE SIGNATURE
 AND SEAL IS AFFIXED SHALL BE ENTERED ON
 THE PLANS IMMEDIATELY UNDER THE
 SIGNATURE OF THE PROFESSIONAL ENGINEER.
 FAC 61G15-23.002(1) & FS 471.025
 11) SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES FOR FIXTURES. INDICATE ON
 PLANS THE SQUARE FOOTAGE FOR EACH
 OCCUPANCY. TABLES 1003.1 & 403.1.
 12) SHT P2.1 HOUSE TRAP NOT APPROVED.
 DELETE FROM DETAIL "B". SECTION 1002.1
 12) SHT P3.1 ALL RISER DIAGRAMS SHALL
 BE
 IN ISOMETRIC FORM AND SHALL REFLECT THE
 FLOOR PLAN. SECTION 104.2.1.
 13) SHT P3.1 WATER RISER ISOMETRIC
 SHALL
 SHOW VALVES REQUIRED BY SECTION
 606.1(4)
 FULL OPEN VALVES ON EVERY DOWN-FEED
 WATER LINE, AND SHOW THE LOCATION OF
 ALL
 WATER HAMMER ARRESTORS REQUIRED BY
 SECTION 604.9 AND SHALL BE LOCATED NEAR
 THE FIXTURE, IN AN "EFFECTIVE RANGE"
 NOT
 IN THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
 14) SHT P3.1 INSPECTION BAY WASTE &
 VENT
 INDICATES A VERTICAL VENT FOR THE 4"
 FD-3 ON RISER DIAGRAM, BUT ON SHT P2.1
 THE VENT IS INDICATED AS A HORIZONTAL
 DRY VENT WHICH IS NOT APPROVED PER
 SECTION 905.3 & 905.4 PLEASE CLARIFY.
 15) A SEPARATE GAS PERMIT IS REQUIRED,
 AND THE FOLLOWING INFORMATION IS
 REQUIRED TO ISSUE THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING
 USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM
 PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 H. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY
 LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS,
 BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK
 AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 K) INDICATE TYPE OF MATERIAL FOR
 REGULATOR VENTS. VENT MATERIAL SHALL BE
 NON COMBUSTABLE. SECTION 631.15
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved