Plan Review Notes
Plan Review Notes For Permit 05010365
Permit Number 05010365
Review Stop M
Sequence Number 1
Notes
Date Text
2005-01-26 00:00:00DENIED:
 1.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) TABLE
 403.3.PLEASE INCLUDE OFFICE AREAS AS
 WELL AS THE GARAGE AREAS.
  
 2.IT IS THE DETERMINATION OF THE
 BUILDING OFFICAL SINCE THIS IS NOT
 CLASSIFIED AS A "REPAIR GARAGE" AND
 SINCE CARS WILL BE MOVED IN AND OUT,
 THAT IT SHALL BE CLASSIFIED AS A
 "PARKING GARAGE".PLEASE SHOW
 COMPLIANCE WITH THE 2001 FBC 411.4.2.
  
 3.PLEASE REFERENCE COMMENTS BY
 ELECTRICAL & BUILDING ON THE SIGNATURER,
 TITLE BLOCK AND CERTIFICATE OF
 AUTHORIZATION FOR THE ARCHITECTURAL &
 ENGINEERING FIRMS (FS 471.023, 471.025 &
 481.219).
  
 4.PLEASE NOTE, PLAN SHEET M2.1
 INDICATES GAS FIRED HEATERS AS WELL
 HORIZONTAL UNIT HEATER (ELECTRIC).
 PLEASE CLARIFY THE PURPOSE OF THE
 ELECTRIC HEATER IN THE MECHANICAL ROOM.
  
  
 5.PROVIDE COMBUSTION AIR CALCULATIONS
 FOR THE GHUH INDICATED ON PLAN SHEETS
 M2.1 & M7.1.
  
 6.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA FOR ALL MECHANICAL
 EQUIPMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.