Plan Review Notes
Plan Review Notes For Permit 05010365
Permit Number 05010365
Review Stop E
Sequence Number 1
Notes
Date Text
2005-01-21 00:00:00************* UNSAT ******************
  
 *PLEASE SEE THIS IS IN FOR "PLAN
 REVIEW"
 ONLY AND NOT SUBMITTED FOR PERMIT.
  
  
 1)NOTE: PLEASE VERIFY LICENSE
 INFORMATION PLACED ON TITLE BLOCK FOR
 FIRM.
 PLEASE SEE THE REQUIRED CA # PER FS
 481.219/471.023 DOES NOT SEEM TO
 CORRELATE WITH STATE WEBSITE. PLEASE SEE
 COPY OF ATTACHED PRINT OUT FROM STATE
 WHICH INDICATES A A DIFFERENT COMPANY
 FOR LICENSE # SHOWN ON PLANS.
  
 2)NOTE: PLEASE SEAL FOR ENGINEER MUST BE
 RAISED,CLEAR AND VISABLE WITH ALL
 INFORMATION ON SAID SEAL AS REQUIRED
 UNDER FS 471.025
 PLEASE ALSO SEE PLANS APPEAR TO BE
 "SIGNED" WITH INITIALS? IF THIS IS
 INDEED THE LEGAL "SIGNATURE" FOR
 ENGINEER, PLEASE PROVIDE A SIGNED,DATED
 AND SEALED NOTORIZED LETTER FOR TO
 AFFIRM LEAGAL SIGNATURE. THIS LTR WILL
 BE PLACED IN OUT SIGNATURE FILE FOR ANY
 POSSIBLE FUTURE REFERENCE.
  
 3)NOTE: PLEASE PROVIDE WIND LOAD
 CALCUALTIONS FOR NEW SITE LIGHTING POLES
 AND FIXTURES. THIS IS REQUIRED AT THIS
 TIME AND MUST MEET FBC 140 MIN.
  
 4)NOTE: PLEASE VERIFY GROUNDING
 ELECTRODE SYSTEM. RISER INDICATES "SEE
 SPEC", YET INFORMATION REQUIRED PER
 250.50 COULD NOT BE LOCATED.
 PLEASE SHOW MIN CWP, FOOTER STEEL AND
 ANY OTHER METAL BLDG AS PART OF GE
 SYSTEM.
  
 5 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE ALSO SEE 220.12 FOR TRACK
 LIGHTING LOADS.
 PLEASE SHOW.
  
 6)NOTE: PLEASE INDICATE MDP AS MCB.
 240.4. 215.5
  
 7)NOTE: PLEASE SEE 2002 NEC ART 511
 PLEASE PLACE NOTE ON PLANS IF "NO
 SERVICE" ON VEHICLES.
  
 PLEASE SEE OTHER POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]