2005-01-31 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 BUILDING |
| |
| 1) MORE INFORMATION IS REQUIRED FOR |
| PLAN |
| REVIEW. APPLICATION DESCRIPTION OF |
| PROJECT IN DETAIL STATES "DIVIDE 2 |
| UNITS |
| INTO OFFICES". IT SEEMS AS IF THERE IS |
| ONE OFFICE ON DRAWING. PLEASE CLARIFY. |
| SECTION 104.2.1. |
| 2) SUBMIT CALCULATIONS FOR MINIMUM |
| FACILITIES PER TABLES 1002.1 AND 403.1. |
| SHOW SQUARE FOOTAGE OF THE |
| SPACE/SPACES. |
| A DRINKING FOUNTAIN IS REQUIRED IN EACH |
| SPACE. |
| 3) ALL INFORMATION AND DRAWINGS SHALL |
| BEAR THE NAME AND SIGNATURE OF THE |
| PERSON RESPONSIBLE FOR THE DESIGN. |
| SECTION 104.2.1. |
| 4) TWO OR MORE COPIES OF SPECIFICATIONS |
| AND DRAWINGS DRAWN TO SCALE WITH |
| SUFFICIENT CLARITY AND DETAIL TO |
| INDICATE THE NATURE AND CHARACTER OF |
| THE |
| WORK SHALL ACCOMPANY THE APPLICATION |
| FOR |
| PERMIT. SECTION 104.2.1. |
| 5) FLOOR PLAN INDICATES A KITCHENETTE. |
| SUBMIT A DETAIL FOR THE KITCHENETTE |
| SHOWING THE LAYOUT OF CABINETS AND |
| FIXTURES. IF THERE IS A SINK IN THE |
| KITCHENETTE IT SHALL BE ACCESSIBLE AND |
| A |
| DETAIL SHOWING COMPLIANCE WITH SECTION |
| 11-4.24 AND ALL SUBSECTIONS. SECTION |
| 104.2.1. |
| 6) IF ANY PLUMBING PIPING IS INSTALLED |
| A |
| SANITARY RISER DIAGRAM AND A WATER |
| RISER |
| DIAGRAM ARE REQUIRED. SHOW ALL PIPE |
| SIZES, CONNECTIONS TO BUILDING DRAIN |
| AND |
| BUILDING WATER SUPPLY, VENTS, VALVES, |
| WATER HAMMER ARRESTORS ECT. SECTION |
| 104.3.1.1. |
| |
| |