Notes
Date Text
2005-01-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 BUILDING
  
 1) MORE INFORMATION IS REQUIRED FOR PLAN
 REVIEW. APPLICATION DESCRIPTION OF
 PROJECT IN DETAIL STATES "DIVIDE 2 UNITS
 INTO OFFICES". IT SEEMS AS IF THERE IS
 ONE OFFICE ON DRAWING. PLEASE CLARIFY.
 SECTION 104.2.1.
 2) SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES PER TABLES 1002.1 AND 403.1.
 SHOW SQUARE FOOTAGE OF THE
 SPACE/SPACES.
 A DRINKING FOUNTAIN IS REQUIRED IN EACH
 SPACE.
 3) ALL INFORMATION AND DRAWINGS SHALL
 BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 SECTION 104.2.1.
 4) TWO OR MORE COPIES OF SPECIFICATIONS
 AND DRAWINGS DRAWN TO SCALE WITH
 SUFFICIENT CLARITY AND DETAIL TO
 INDICATE THE NATURE AND CHARACTER OF THE
 WORK SHALL ACCOMPANY THE APPLICATION FOR
 PERMIT. SECTION 104.2.1.
 5) FLOOR PLAN INDICATES A KITCHENETTE.
 SUBMIT A DETAIL FOR THE KITCHENETTE
 SHOWING THE LAYOUT OF CABINETS AND
 FIXTURES. IF THERE IS A SINK IN THE
 KITCHENETTE IT SHALL BE ACCESSIBLE AND A
 DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.24 AND ALL SUBSECTIONS. SECTION
 104.2.1.
 6) IF ANY PLUMBING PIPING IS INSTALLED A
 SANITARY RISER DIAGRAM AND A WATER RISER
 DIAGRAM ARE REQUIRED. SHOW ALL PIPE
 SIZES, CONNECTIONS TO BUILDING DRAIN AND
 BUILDING WATER SUPPLY, VENTS, VALVES,
 WATER HAMMER ARRESTORS ECT. SECTION
 104.3.1.1.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]