Plan Review Notes
Plan Review Notes For Permit 05010308
Permit Number 05010308
Review Stop E
Sequence Number 1
Notes
Date Text
2005-01-11 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SEE FBC 104.2.1 .
 PLEASE SEE ALL PLANS/D RAWINGMUST
 CONTAIN PRINTED NAME AND SIGNATURE OF
 PERSON RESPONSIBLE FOR PLANS.
  
 2)NOTE: PLEASE SEE PERMIT APPLICATION
 MENTIONS TO SPLIT 2-UNITS INTO OFFICES?
 PLEASE CLARIFY.
  
 3)NOTE: PLEASE SUBMIT MIN ELECTRICAL
 REQUIRED FOR NEW OFFICE AREAS LTS? EM
 LTS? ANY EXT LTS REQUIRED.
 NEC 700, 215.5
 ALL NEW ELECTRICAL TO BE SHOWN AND ALL
 CIRCUITING TO PLACES ON PLANS AND
 CORRELATE WITH PANEL SCHEDULE TO BE
 SUBMITTED.
 IF CREATEING TWO NEW SPACES, PLEASE SEE
 MIN SEPARATION REQUIRED FOR EELCTRICAL
 CIRCUITING/ BOXES ETC.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]