Plan Review Notes
Plan Review Notes For Permit 05010308
Permit Number 05010308
Review Stop B
Sequence Number 1
Notes
Date Text
2005-01-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05010308
 ADD: 4047 OKEECHOBEE BLVD
 SUITE 2002& 2003
 CONT: CAREY BENJAMIN PROPERTIES
 TEL: (561)723-1249
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) THE VALUE INDICATED ON THE PERMIT
 APPLICATION IS TO LOW FOR THE AMOUNT OF
 WORK INDICATED ON THE PLANS. IF VALUE
 ISN'T INCREASE TO THE CORRECT VALUE THE
 CITY WILL CALCULATE THE VALUE USING
 MARSHALL & SWIFT TO CALCULATE VALUE.
  
 2)ALL INFORMATION, DRAWINGS, SPECIF-
 ICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 CITY AMENDMENTS 104.2.1
  
 3) IF THE VALUE OF THE CALCULATED WORK
 SHALL BE ABOVE $25,000.00 FL S. S.
 481.229(C) STATES PLANS ARE TO BE
 SUBMITTED TO THE BUILDING DEPARTMENT
 MUST USE THE SERVICES OF A REGISTERED
 FL
 ARCHITECT.
  
 4) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 5) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO
 THE
 AUTHORITY HAVING JURISDICTION. SUCH
 IDEN
 TIFICATION SHALL BE ABOVE ANY
 DECORATIVE
 CEILING CEILING AND IN CONCEALED
 SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 6) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
  
 7) PLANS DO NOT INDICATE DOOR
 CLEARENCES
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING
 CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 8) 11-4.13.5 DOORWAYS, MINIMUM CLEAR
 WIDTH: DOORWAY SHALL HAVE A MINI- MUM
 CLEAR OPENING OF 32" WITH THE DOOR OPEN
 90 DEGREES, MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE OPPOSITE STOP.
  
 9) 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 10) THE WIDTH OF THE CORRIDORS SEE
 TABLE 1004.
  
 11)1016.3.1. EXIT SIGNS:
 EXIT SIGNS SHALL BE MARKED BY AN
 APPROVED SIGN READILY VISIBLE FROM ANY
 DIRECTION OF EXIT ACCESS. EVERY EXIT
 SIGN SHALL BE SUITABLE ILLUMINATED BY A
 RELIABLE LIGHT SOURCE. EXTERNALLY AND
 INTERNALLY ILLUMINATED SIGNS SHALL BE
 VISIBLE IN BOTH THE NORMAL & EMERGENCY
 LIGHTING.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026