Plan Review Notes
Plan Review Notes For Permit 05010275
Permit Number 05010275
Review Stop B
Sequence Number 1
Notes
Date Text
2005-01-07 00:00:00BUILDING PLAN REVIEW FAILED:
  
 1. ACCORDING TO THE FBC 2001 IF YOU
 REPLACE MORE THAN 25% OF THE GLASS AREA
 IN A BUILDING YOU MUST PROVIDE STORM
 PANELS FOR THE NEW WINDOWS OR INSTALL
 IMPACT GLASS WINDOWS.
  
 2. YOU MUST SUBMIT 2 COPIES OF THE
 PRODUCT APPROVALS FOR PERMITTING.ONLY
 ONE COPY OF THE DADE COUNTY APPROVALS
 WERE SUBMITTED.
  
 3. PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 WWW.FLORIDABUILDING.ORG
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUIDLING PLANS EXAMINER
 805-6713