Plan Review Notes
Plan Review Notes For Permit 05010235
Permit Number 05010235
Review Stop E
Sequence Number 1
Notes
Date Text
2005-01-18 00:00:00*********** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 SHOWING ALL EXISTING AND NEW LOADS ADDED
 TO SERVICE.
 215.5,220.31B
 PLEASE SEE ALL CONTINOUS LOADS ARE TO BE
 SHOWN AT 125%. PUMP, HEAT PUMP,,,
  
 **** NOTE****
 ALL PLANS/DRAWINGS MUST CONTAIN THE
 PRINTED NAME AND SIGNATURE OF PERSON
 RESPONSIBLE FOR PLANS. FBC 104.2.1
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.