2005-08-18 00:00:00 | BUILDING REVIEW THIRD CHECKLIST: |
| 1- DESIGNER OF RECORD TO SPECIFY IN THE |
| DWGS THE ROOF TILE FASTENING AS REQ'D BY |
| SEC. 104.2.1.1 CITY AMENDMENTS TO FBC |
| 2001. IT'S THE DESIGNER RESPONSIBILITY, |
| NOT THE BUILDER. |
| |
| 2- REVISE FASTENERS FOR THD210 |
| CONNECTOR. SEE TECHNICAL BULLETIN. |
| |
| 3- BBQ WILL NOT BE INSTALLED AT THIS |
| TIME. FUTURE INSTALLATION AS MENTIONED |
| IN PLANS WILL REQUIRE SEPARATE PERMIT TO |
| VERIFY COMPLIANCE OF BBQ SPECS FOR PORCH |
| INSTALLATION. SEC. 2808 FBC 2001. |
| |
| 4- CLARIFY IF USING STORM SHUTTERS OR |
| IMPACT GLAZING. THERE IS A NOTE THAT |
| SHUTTERS UNDER SEPARATE PERMIT, WHILE, |
| PRODUCT APPROVAL SUBMITTED FOR CASEMENT |
| WINDOWS IS FOR IMPACT WINDOWS. CLARIFY |
| AND PROVIDE COMPLETE CONSISTENT |
| INFORMATION FOR EITHER METHOD. |
| |
| 5- OWES $334.26 FOR 2ND SUBMITTAL. NOTE: |
| ADDITIONAL RE-SUBMITTAL FEES WILL APPLY. |
| |
| 6- NOC WAS RE-RECORDED ON 5-20-05. MAY |
| NEED TO BE RE-RECORDED AFTER 90 DAYS. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ AT (561)805-6712. |