Plan Review Notes For Permit 04121890 |
Permit Number |
04121890 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-06-02 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | | | 1} INDICATE THE LOCATION OF PANEL | | "B"&"C". | | | | 2} INDICATE LOCATION OF OVERCURRENT | | PROTECTION FOR PANELS "A" & "B". | | | | 3} THE OCP FOR CIRCUITS 11,12 PANEL "A", | | 12,13,14,15 PANEL "B" IS TOO LARGE FOR | | THE CONDUCTORS PER 210.16. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|