2005-06-08 00:00:00 | BUILDING REVIEW CHECKLIST: |
| |
| 1- DESIGNER OF RECORD TO SPECIFY ROOF |
| TILE FASTENING AS REQUIRED BY SECTION |
| 104.2.1.1 CITY AMENDMENTS TO FBC 2001. |
| |
| 2- USP CONNECTOR THD210 AND THD210-2 IS |
| A WOOD TO WOOD CONNECTOR. NEED MASONRY |
| CONNECTOR. SEE CATALOGUE FOR PROPER |
| MASONRY CONNECTOR AND REVISE AS REQUIRED |
| |
| 3- BBQ INFORMATION SUBMITTED WILL BE |
| FORWARDED TO BUILDING OFFICIAL FOR |
| APPROVAL. |
| NOTE: THERE ARE SOME COMPANIES WHO HAVE |
| BBQ'S SPECIFICALLY DESIGNED FOR PORCHES |
| OR LANAIS. THEY REQUIRE EXHAUST HOOD. |
| BUILDING OFFICIAL MAY ASK FOR ADDITIONAL |
| INFORMATION OR TESTING TO SUPPORT |
| ALFRESCO GRILLS' LETTER STATEMENT THAT |
| HOOD IS NOT REQUIRED. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| |
| 4- WINDOW MULLIONS: CLEARLY SPECIFY |
| MULLION SIZE AND ANCHORS TO BE USED TO |
| VERIFY ADEQUACY WITH CALCS FOR DESIGN |
| PRESSURES AT OPENINGS. |
| |
| 5- STORM SHUTTERS: A) REVISE MIN. PANEL |
| SIZE. SEE ENGINEERED DRAWINGS |
| LIMITATIONS ACCORDING TO THE MOUNTING |
| CONDITIONS. |
| |
| B) REVISE HEIGHT FOR OPENINGS #13 AND |
| #14. SEE PLANS FOR OPENINGS. |
| NOTE: CHECK FOR MAX. PANEL SPAN. |
| |
| C) REVISE DESIGN PRESSURES FOR OPENING |
| #13. SEE PLANS. |
| NOTE: CHECK FOR MAX. PANEL SPAN. |
| |
| 6- DADE COUNTY NOA REPORT FOR CASEMENT |
| WINDOWSDOESN'T MATCH NOA SUBMITTED FOR |
| FLORIDA PRODUCT APPROVAL. RESUBMIT |
| CORRECT ONE. |
| |
| 7- DADE COUNTY NOA REPORT FOR CONCRETE |
| LINTELS DOESN'T MATCH ONE SUBMITTED FOR |
| FLORIDA PRODUCT APPROVAL. RESUBMIT |
| CORRECT ONE. |
| |