2005-06-08 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENING AS REQUIRED BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
  
 2- USP CONNECTOR THD210 AND THD210-2 IS
 A WOOD TO WOOD CONNECTOR. NEED MASONRY
 CONNECTOR. SEE CATALOGUE FOR PROPER
 MASONRY CONNECTOR AND REVISE AS REQUIRED
  
 3- BBQ INFORMATION SUBMITTED WILL BE
 FORWARDED TO BUILDING OFFICIAL FOR
 APPROVAL.
 NOTE: THERE ARE SOME COMPANIES WHO HAVE
 BBQ'S SPECIFICALLY DESIGNED FOR PORCHES
 OR LANAIS. THEY REQUIRE EXHAUST HOOD.
 BUILDING OFFICIAL MAY ASK FOR ADDITIONAL
 INFORMATION OR TESTING TO SUPPORT
 ALFRESCO GRILLS' LETTER STATEMENT THAT
 HOOD IS NOT REQUIRED. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 4- WINDOW MULLIONS: CLEARLY SPECIFY
 MULLION SIZE AND ANCHORS TO BE USED TO
 VERIFY ADEQUACY WITH CALCS FOR DESIGN
 PRESSURES AT OPENINGS.
  
 5- STORM SHUTTERS: A) REVISE MIN. PANEL
 SIZE. SEE ENGINEERED DRAWINGS
 LIMITATIONS ACCORDING TO THE MOUNTING
 CONDITIONS.
  
 B) REVISE HEIGHT FOR OPENINGS #13 AND
 #14. SEE PLANS FOR OPENINGS.
 NOTE: CHECK FOR MAX. PANEL SPAN.
  
 C) REVISE DESIGN PRESSURES FOR OPENING
 #13. SEE PLANS.
 NOTE: CHECK FOR MAX. PANEL SPAN.
  
 6- DADE COUNTY NOA REPORT FOR CASEMENT
 WINDOWSDOESN'T MATCH NOA SUBMITTED FOR
 FLORIDA PRODUCT APPROVAL. RESUBMIT
 CORRECT ONE.
  
 7- DADE COUNTY NOA REPORT FOR CONCRETE
 LINTELS DOESN'T MATCH ONE SUBMITTED FOR
 FLORIDA PRODUCT APPROVAL. RESUBMIT
 CORRECT ONE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.