2005-01-07 00:00:00 | | | | | .PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE OVERCURRENT PROTECTION FOR AHU | | #2 AT 60 AMPS IS TOO LARGE TO PROTECT A | | 5KW UNIT.(5000X125%/240=26 AMPS, MAX 30 | | AMP OCP). ALSO 60 AMP OCP SHOWN INTHE | | MAIN PANEL SEEM TOOLARGE FOR THE | | CONDENSING UNIT. SEE ARTICLE 440.22 | | NEC. | | | | 2} THERE ARE NO PROVISIONS IN THE | | CALCULATIONS FOR POOL EQUIPMENT, BUT | | THERE IS EQUIPMENT SHOWN ON THE PLAN. | | | | 3} IF NOTE #15 IS ADHERED TO, THOSE | | CIRCUITS WOULD HAVE TO BE PROTECTED BY | | AN AFCI BECAUSE THE DETECTORS ARE | | LOCATED IN BEDROOMS. 210.12. | | | | 4} THE GFI'S SHOWN IN THE DINING ROOM | | AND BREAKFAST NOOK, WHILE NOT REQUIRED | | ALTHOUGH PERMISSIBLE, MUST BE INSTALLED | | IF LEFT ON THE PLAN. | | | | 5} A RECEPTACLE NEEDS TO BE ADDED TO | | THE | | MASTER BEDROOM TO COMPLY WITH | | 210.52(A). | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|