2005-03-11 00:00:00 | BUILDING REVIEW CHECKLIST: |
| |
| 1- MISSING SHEET A-4. |
| THERE ARE 2 A-5 SHEETS. ONE OF THE IS |
| FOR A 2 STORY HOUSE. |
| THERE ARE 2 CV-1 SHEETS. PROVIDE ONLY |
| ONE PER SET. |
| |
| 2- UPDATE TRUSS ANCHOR SCHEDULE TO MATCH |
| CAPACITY AND TYPE & NUMBER OF FASTENERS |
| AS SHOWN ON FLORIDA PRODUCT APPROVAL |
| PACKAGE. OR PROVIDE COMPLETE ENGINEERING |
| ANALYSIS AND CALCULATIONS THAT COMPLY |
| WITH SECTION 1609.4.3 FBC 2001. |
| |
| 3- PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL FOR: |
| A) USP TRUSS ANCHORS SPECIFIED ON PLANS. |
| |
| B) ENTRY DOORS WITH SIZE AND DIRECTION |
| OF SWING AS SHOWN ON PLANS. AND EXACT |
| SAME DRAWINGS THAT WERE SUBMITTED FOR |
| FLORIDA PRODUCT APPROVAL. |
| NEED SOLID DOOR OR IMPACT GLAZING |
| BECAUSE DOOR IS TO BE USED FOR EMERGENCY |
| EGRESS. SEC. 1005.4.5 FBC 2001. |
| |
| C) FRENCH DOORS WITH SIZE AND SWING |
| DIRECTION AS SHOWN ON PLANS. AND WITH |
| EXACT SAME DRAWINGS THAT WERE SUBMITTED |
| FOR FLORIDA PRODUCT APPROVAL. |
| |
| D) CASEMENT WINDOWS WITH EXACT SAME |
| DRAWINGS THAT WERE SUBMITTED FOR FLORIDA |
| PRODUCT APPROVAL. |
| |
| 4- DELETE BBQ AND FIREPLACE FROM |
| DRAWINGS IF OPTION IS NOT GOING TO BE |
| BUILT OR PROVIDE COMPLETE INFORMATION |
| FOR THEM AS REQUIRED BY SEC. 2806 AND |
| 2808 FBC 2001. |
| |
| 5- STORM SHUTTERS: A) BOTH COPIES NEED |
| TO HAVE ORIGINAL SEAL, SIGNATURE AND |
| DATE AS REQUIRED BY ENGINEER ON NOTE #6. |
| |
| B) SOME PANELS EXCEED MAX. PANEL SPAN |
| ACCORDING TO THE DESIGN PRESSURES. SEE |
| ENGINEERED DRAWINGS AND REVISE AS |
| REQUIRED. |
| |
| C) CLEARLY MARK ON ENGINEERED DRAWINGS |
| THE SPECIFIC ANCHOR TYPE AND SPACING TO |
| BE USED ACCORDING TO THE EDGE DISTANCE, |
| PANEL SPAN, DESIGN PRESSURES, CONNECTION |
| TYPE AND STRUCTURE TO BE ATTACHED TO |
| (MASONRY OR 2500PSI CONCRETE). |
| |